12.5 Models of linear nozzles and typical
installations
humidi er model: UR002 UR004 UR006 UR010 UR013 UR020 UR027 UR040 UR053 UR060 UR080
ø of steam outlet mm (in): 30 (1.2”) 40 (1.6”) 2x40 (1.6”)
maximum capacity kg/h (lb/h):
2
(4.4)
4
(8.8)
6
(13.2)
10
(22)
13
(28.6)
20
(44)
27
(59.5)
40
(88)
53
(116.8)
60
(132.2)
80
(176.36)
"nozzle steam
inlet ø mm (in)”
maximum nozzle
capacity kg/h
(lb/h)
length
of nozzle mm (in)
code
30 (1.2”) 5 (11) 350 (13.7) DP035D30R0 1 1
30 (1.2”) 8 (17.6) 450 (17.7) DP045D30R0 1 1 1
30 (1.2”) 12 (26.4) 600 (23.6) DP060D30R0 1 1 1 (2)*
30 (1.2”) 18 (39.6) 850 (33.5) DP085D30R0 1111(2)* (2)*
30 (1.2”) 18 (39.6) 1050 (41.3) DP105D30R0 1111(2)* (2)*
30 (1.2”) 18 (39.6) 1250 (49.2) DP125D30R0 1111(2)* (2)*
30 (1.2”) 18 (39.6) 1650 (65) DP165D30R0 1 1 (2)* (2)*
40 (1.6”) 25 (55) 850 (33.5) DP085D40R0 1 1 (2)** (4)** (4)** (4)**
40 (1.6”) 35 (77) 1050 (41.3) DP105D40R0 1 1 (2)** 2 2 (4)**
40 (1.6”) 45 (99) 1250 (49.2) DP125D40R0 1 1122 2
40 (1.6”) 45 (99) 1650 (65) DP165D40R0 1122 2
40 (1.6”) 45 (99) 2050 (80.7) DP205D40R0 1 2 2 2
Tab. 12.e
For typical installations of linear distibutors see  gure 11.f on page 36.
70 mm
min. 200 mm
1
1/3 H
H > 250 mm
2
1/3 H
200 mm
H > 250 mm
3
1/5 H
2/5 H
200 mm
H > 350 mm
4
1/5 H
2/5 H
H > 400 mm
5
1/7 H
2/7 H
2/7 H
H > 500 mm
6
1/7 H
2/7 H
2/7 H
H > 600 mm
7
min 200 mm
=
=
8
H > 200 mm
=
=
1/2 H
9