EasyManua.ls Logo

Carel heaterSteam UR006 - 8. Configuration Parameters; Parameter Access and Setting Guide; Basic Operation Parameters Overview; Auxiliary Function Parameters

Carel heaterSteam UR006
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
ENG
“heaterSteam +0300075EN - rel. 1.2 - 29.09.2015
8. CONFIGURATION PARAMETERS
8.1 Parameter access and setting
See chapter 6 “Start and user interface
Note: variable type: A = analog I=full, D = digital.
8.2 Basic operation parameters
Par. Description UM range def
Variable
type
CAREL
protocol
notes
A0 Operating mode 0,…,3 2 l 9
0= ON/OFF command
1= external proportional signal
2= autonomous adjusting with room probe
3= autonomous adjusting with room probe and limit probe
A1 Unit of measurement: 0,1 0 l 10 0=°C, kg/h – 1 = °F, Ib/h
A2
signal applied to room probe input
autonomous control (A0=1, 2 or 3)
0,…, 4 0 I 11
0= 0…1 V
1= 0…10 V
2= 2…10 V
3= 0…20 mA
4= 4…20 mA
A3 room probe minimum %rH 0, .., (A4) 0 I 12 can only be accessed in autonomous control (A0=2 or 3)
A4 room probe maximum %rH (A3), .., 255 * 100 I 13
A5 room probe calibration %rH -10.0,…,10.0 0 A 4
A6
signal applied to the outlet probe
input can only be accessed in
autonomous control with outlet
probe (A0=3)
0,…,4 0 I 14
0= 0…1 V
1= 0…10 V
2= 2…10 V
3= 0…20 mA
4=4…20 mA
A7 minimum limit probe %rH 0,…,(A8) 0 I 15 can only be accessed in autonomous control with outlet probe (A0=3)
A8 maximum limit probe %rH (A7), .., 100 100 I 16
A9 limit probe calibration %rH -10…10 0 A 5
Tab. 8.a
8.3 Auxiliary function parameters
Par. Description UM range def
Variable
type
CAREL
protocol
notes
b0 period of modulation (if set to 0 modulation is disabled) s 0,…,199 ** I 17
b1 Check the functions assigned to parameter b1 in the table given in chapter 12. 0…63 0 I 18
b2 start pre-heating o set (referred to set point) %% r.H. 2,…,19.9 3.0 A 6
They can only
be accessed
with pre-heating
function enabled
(b1=1 or 3)
b3 pre-heating temperature °C 70,…,90 80 I 19
b5 conductivity pre-alarm threshold (displayed as 1•2) µS/cm 0,…,2000 1250 I 21
b6 conductivity alarm threshold (displayed as 1•5) µS/cm 0,…,2000 1500 I 22
b7 control of the foam detection threshold (if set to 0 foam detection is disabled) % 0,…,100 50 I 23
b8
setting the maximum number of evaporation cycles between two drain cycles for
dilution step:1
The actual value used is internally calculated based on the value read for the conduc-
tivity of the water supply (the higher the conductivity, the lower the calculated value),
however if the calculated value is greater than b8, b8 will be used. If b8=0, it shall
be automatically set to 2 at  rst heaters start-up and if conductivity measured in the
supply water is <= 100 µS/cm, or at 5.
- 0…50 0 I 33
b9 minimum time for passing from 0 to 100% of steam production min 0,…,100 0 I 24
bA percentage reduction in the duration of the water  ll time % 20…100 100 I 34
bb
steam production value (step 0.1%)
it allows the user to “adjust” the value displayed by parameter d3, if there is a system
available for measuring the di erence between the value displayed d3 and the actual
steam production.
Example of use:
d3= 10 kg/h and bb= +10% changes d3 to 11 kg/h (= 10 kg/h + 10%)
% -19.9…19.9 0 A 7
bC automatic total drain for inactivity (see par. 12) days 1…199 3 I 35
bd user-adjustable duration of dilution drain (see par. 12) % 0…190 100 I 36
bE ll-up cycle duration, after dilution drain, in pwn mode s 1…199 5 I 37
Tab. 8.b

Table of Contents

Related product manuals