Cod. +030220151 - Rel. 2.1 - 04/09/98
46
SUMMARY OF ALL THE PARAMETERS
SENSOR PARAMETERS Type Min Max Unit Def New
/0 Type of sensor (0=NTC,1=PTC) C 0 1 - 0
/C Calibration F -20 +20 °C/°F 0.0
/2 Measurement stability C 1 15 - 4
/3 Sensor reading speed C 1 15 - 8
/4 Virtual sensor C 0 100 0
/5 °C /°F (0=°C, 1=°F) C 0 1 flag 0
/6 Decimal point (0=yes, 1=no) C 0 1 flag 0
CONTROL PARAMETERS Type Min Max Unit Def New
rd Control differential F 0.1 19.9 °C/°F 2
r1 Minimum set allowed C -40 r2 °C/°F -40
r2 Maximum set allowed C r1 199 °C/°F 90
r3 Direct / Reverse operation (Direct r3=0, Reverse r3=1) C 0 1 flag 0
COMPRESSOR PARAMETERS Type Min Max Unit Def New
c0 Compressor start-up delay after unit start-up C 0 15 min 0
c1 Minimum interval between two compressor start-up C 0 15 min 0
c2 Minimum compressor off-time C 0 15 min 0
c3 Minimum compressor on-time C 0 15 min 0
c4 Duty setting (compressor safety, 0=OFF,100=ON) C 0 100 min 0
cc Duration of continuos cycle C 0 15 hrs 4
c6 Alarm cut-out after continuos cycle C 0 15 hrs 2
DEFROST PARAMETERS Type Min Max Unit Def New
d0 Type of defrost (0=resistance, 1= hot gas) C 0 1 flag 0
dI Interval between defrost F 0 199 hrs 8
dt End defrost temperature set F -40 199 °C/°F 4
dP Maximum duration of defrost F 1 199 min 30
d4 Defrost on unit start-up (0=no, 1=yes) C 0 1 flag 0
d5 Defrost delay after unit start-up or multi-function input C 0 199 min 0
d6 Display override during defrost (0=no, 1=yes) C 0 1 flag 1
dd Dripping time F 0 15 min 2
d8 Duration of alarm cut-out after defrost and/or opening door F 0 15 hrs 1
d9 Defrost has priority over compressor protection (0=no, 1=yes) C 0 1 flag 0
d/ Defrost sensor reading F - - °C/°F -
dC Time basis (0=hrs/mins, 1=minutes/seconds) C 0 1 flag 0