EasyManua.ls Logo

Carel µC2

Carel µC2
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
E N G L I S H
µC
2
- +030220731 - rel. 1.2 - 26.10.2007
4.3.2 Antifreeze/auxiliary heater setting parameters (A*)
display
indicat.
parameter and description default
level
min. max. U.O.M. variat. default visibility supervis.
variable
Modbus variabile
type
A01 Antifreeze/low ambient temp. (air/air) alarm set point U A07 A04 °C/°F 0.1 3.0 - 11 (R/W) 11 Analog
A02 Differential for antifreeze/low ambient temperature alarm U 0.3 122.0 °C °F 0.1 5.0 - 12 (R/W) 12 Analog
A03
Bypass time for antifreeze alarm/low ambient temp. when turning on the unit
in heating mode
U 0 150 S 1 0 - 22 (R/W) 150 Integer
A04 Set point for the activation of antifreeze heater/auxiliary heater U A01 r16 °C/°F 0.1 5.0 - 13 (R/W) 13 Analog
A05 Diff. for antifreeze heater/auxiliary heater U 0.3 50.0 °C/°F 0.1 1.0 - 14 (R/W) 14 Analog
A06 Auxiliary heater probe
0= Control probe see (Table 5.a)
1= Antifreeze probe see (Table 5.a)
F 0 1 Flag 1 0 - 6 (R/W) 6 Digital
A07 Antifreeze alarm set point limit F -40.0 176.0 °C °F 0.1 -40.0 - 15 (R/W) 15 Analog
A08 Auxiliary heater set point in heating mode U A01 r16 °C °F 0.1 25.0 - 16 (R/W) 16 Analog
A09 Auxiliary heater differential in heating mode U 0.3 50.0 °C/°F 0.1 3.0 - 17 (R/W) 17 Analog
A10 Antifreeze automatic start up
0= disabled function
1= Heaters and pump on at the same time on A4/A8
2= Heaters and pump on indipendently on A4/A8
3= Heaters ON on A4/A8
U 0 3 Flag 1 0 - 23 (R/W) 151 Integer
Table 4.b
4.3.3 Probe reading parameters (B*)
display
indicat.
parameter and description default
level
min. max. U.O.M. variat. default visibility supervis.
variable
Modbus variabile
type
b00 Config. of probe to be shown on the display
0= probe B1
1= probe B2
2= probe B3
3= probe B4
4= probe B5
5= probe B6
6= probe B7
7= probe B8
8= set point without compensation
9= dynamic set point with possible compensation
10= remote ON/OFF digital input status
U 0 10 Flag 1 0 - 24 (R/W) 152 integer
b01 Value read by probe B1 D - - °C /°F - - - 70 (R) 70 Analog
b02 Value read by probe B2 D - - °C /°F - - - 71 (R) 71 Analog
b03 Value read by probe B3
D - - °C /°F - - - 72 (R) 72 Analog
b04 Value read by probe B4 D - - °C /°F/bar - - - 73 (R) 73 Analog
b05 Value read by probe B5 D - - °C /°F - - X 74 (R) 74 Analog
b06 Value read by probe B6 D - - °C /°F - - X 75 (R) 75 Analog
b07 Value read by probe B7 D - - °C /°F - - X 76 (R) 76 Analog
b08 Value read by probe B8 D - - °C /°F bar - - X 77 (R) 77 Analog
b09 Driver 1 evaporator temperature D - - °C /°F - - V 78 (R) 78 Analog
b10 Driver 1 evaporator pressure D - - bar - - V 79 (R) 79 Analog
b11 Driver 1 superheating D - - °C /°F - - V 80 (R) 80 Analog
b12 Driver 1 saturation temperature D - - °C /°F - - V 81 (R) 81 Analog
b13
Driver 1 valve position D 0 100.0 % - - V 82 (R) 82 Analog
b14 Driver 2 evaporator temperature D - - °C /°F - - XV 83 (R) 83 Analog
b15 Driver 2 evaporator pressure D - - bar - - XV 84 (R) 84 Analog
b16 Driver 2 superheating D - - °C /°F - - XV 85 (R) 85 Analog
b17 Driver 2 saturation temperature D - - °C /°F - - XV 86 (R) 86 Analog
b18 Driver 2 valve position D 0 100.0 % - - XV 87 (R) 87 Analog
b19 Temp. probe at the outlet of the external coil c1 D - - °C /°F - - V 88 (R) 88 Analog
b20 Temp. probe at the outlet of the external coil c12 D - - °C /°F - - XV 89 (R) 89 Analog
Table 4.c
4.3.4 Compressor setting parameters (c*)
display
indicat.
parameter and description default
level
min. max. U.O.M. variat. def. visibi-
lity
supervis.
variable
Modbus variabile
type
c01 Min. compressor ON time U 0 999 s 1 60 - 25 (R/W) 153 Integer
c02 Min. OFF time compressor U 0 999 s 1 60 - 26 (R/W) 154 Integer
c03
Delay between 2 starts of the same compressor U 0 999 s 1 360 - 27 (R/W) 155 Integer
c04 Delay between starts of the 2 compressors U 0 999 s 1 10 - 28 (R/W) 156 Integer
c05 Delay between 2 shut-downs of the 2 compressors U 0 999 s 1 0 - 29 (R/W) 157 Integer
c06 Delay at start-up U 0 999 s 1 0 - 30 (R/W) 158 Integer
c07 Delay in switching on the compressor after switching on the pump/inlet
fan (air/air)
U 0 150 s 1 20 - 31 (R/W) 159 Integer
c08 Delay in switching OFF the compressor after switching OFF the pump/
inlet fan (air/air)
U 0 150 min 1 1 - 32 (R/W) 160 Integer
c09 Maximum compressor operating time in tandem U 0 60 min 1 0 - 33 (R/W) 161 Integer
c10 Compressor 1 timer D 0 800.0 100 hours 0.1 0 - 90 (R) 90 Analog
c11 Compressor 2 timer D 0 800.0 100 hours 0.1 0 - 91 (R) 91 Analog
c12 Compressor 3 timer D 0 800.0 100 hours 0.1 0 - 92 (R) 92 Analog
c13
Compressor 4 timer D 0 800.0 100 hours 0.1 0 - 93 (R) 93 Analog
c14 Operation timer threshold U 0 100 100 hours 1 0 - 34 (R/W) 162 Integer
c15 Hour counter evaporator pump/fan 1 D 0 800.0 100 hours 0.1 0 - 94 (R) 94 Analog
c16 Hour counter condenser backup pump/fan 2 D 0 800.0 100 hours 0.1 0 - 95 (R) 95 Analog
c17 Minimum time between 2 pump starts U 1 150 min 1 30 - 35 (R/W) 163 Integer
c18 Minimum pump ON time U 1 15 min 1 3 - 36 (R/W) 164 Integer
Table 4.d

Other manuals for Carel µC2

Related product manuals