- Minimum Cooling set point
r13: Establishes the minimum limit for setting the Cooling set point.
- Maximum Cooling set point
r14: Establishes the maximum limit for setting the Cooling set point.
- Minimum heating set point
r15: Establishes the minimum limit for setting the heating set point.
- Maximum heating set point
r16: Establishes the maximum limit for setting the heating set point.
- Cooling compensation constant (chiller mode):
r17: Sets the coefficient that controls the cooling compensation algorithm. In cooling mode, if r17 is
positive, the set point increases as the outside temperature increases (measured by the outside probe); if
on the other hand r17 is negative the set point decreases as the outside temperature increases.
This difference in the set point from the set value can have a maximum absolute value equal to the set
-
ting of r18. The values for the parameters shown on the graph are: r17=±2, r01=25, r19=32 and r18=5).
Key:
1. temperature;
2. time;
3. external temperature (probe B3/B4);
4. comp. start temperature (r19);
5. positive compensation (r17= 2);
6. set point (r1);
7. negative compensation (r17=-2).
Fig. 5.b.i
- Maximum deviation from the set point
r18: Indicates the maximum deviation from the set point beyond which compensation is stopped (maxi-
mum and minimum limits in reference to the set point).
- Start compensation temperature in cooling (outside probe)
r19: Sets the temperature (measured by the outside probe) above which the compensation function
starts (cooling), value between -40T80 °C.
- Start compensation temperature in heating (outside probe)
r20: Sets the temperature (measured by the outside probe) below which the compensation function
starts (heating), the value must be between -40T80 °C.
- Second cooling set point from external contact
r21: Represents the alternative to r01 if an associated digital input is closed (see parameter P08), between
r13 and r14.
- Second heating set point from external contact
r22: Represents the alternative to r03 if an associated digital input is closed (see parameter P08), between
r15 and r16.