3ODQW:DWFK
Cod. Carel. +030221221 – rel. 1.0 dated 20/02/01
27
6FUHHQFRGH 'HVFULSWLRQ /HYHO 7\SH 'HIDXOW 0LQ0D[
a4 Variables log: log full alarm 3 flag Enabled Enabled
Disabled
a5 Variables log: reset free space indicator 3 flag Serial
download
Serial download
Print report
g1 Installation name 2 string Pwatch
g1 Installation code 2 1 1-65535
g2 Type of unit for instrument configuration 3 flags Ir32, Ir32c...
g2 unit category X 32 3 flags - List of names
g2 unit description X 32 3 flags - List of names
g2 unit progressive no. X 32 3 0 1÷32
g3 self-configuration mode activation 3 flag disabled
g4 Baud rate used on RS485 serial line to
peripherals
3 Baud 19200 1200÷19200
g5 level 1 access password 3 0001 0÷65535
g5 level 1 user name 3 string “User1”
g5 level 2 access password 3 0002 0÷65535
g5 level 2 user name 3 string “User2”
g5 level 3 access password 3 0003 0÷65535
g5 level 3 user name 3 string “User3”
g6 status screen rotation activation 2 flag Disabled Enabled
Disabled
L1 Language selection 2 flags English English
Italian
German
French
Spanish
m1 Serial port mode, internal modem/external
modem/direct serial connection
3 flags internal modem No modem
internal modem
external modem
m1 Number dialling pulse/tone 3 flag Tone Tone / Pulse
M1 Modem type 3 flags PSTN PSTN
GSM Type 1
GSM Type 2
m2 data processing centre telephone number 2 string
m2 enable data processing centre telephone
number
2 flags Disabled Enabled
Disabled
m3 data processing centre access password 3 number 00004
m3 data processing centre access user name 3 string “RemoteUser”
m4 Enable call to data processing centre to
send alarms
3 flag Disabled Enabled
Disabled
m4 Enable call to data processing centre to
download variables log
3 flag Disabled Enabled
Disabled
m5 fax number 1 2 string 0000...
m5 fax number 2 2 string 0000...
m5 fax number 3 2 string 0000...
m5 enable fax number 1 2 Assint Disabled -, A
m5 enable or force fax number 2 2 Assint Disabled -,b,B
m5 enable or force fax number 3 2 Assint Disabled -,c,C
m7 PIN for GSM modem 3 string
m8 Enable SMS transmission 3 flag Disabled Enabled
Disabled
m8 Telephone number of the network
operator’s SMS service centre
3 string 0000...
m9 Password for connection to TAP SMS
service centre
2 string
m9 Baudrate for connection to SMS service
centre
2 Baud 19200 1200-38400
m9 T
yp
e of
p
rotocol for connection to SMS 2 flags UCP UCP-TAP

Related product manuals