3ODQW:DWFK
Cod. Carel. +030221221 – rel. 1.0 dated 20/02/01
26
 3$5$0(7(56$1'&21),*85$7,21352&('85(
 3DUDPHWHUSURJUDPPLQJ
The parameter programming procedure is accessed by pressing the 3UJ button for 3 seconds. The various levels of parameters
are accessed by entering different passwords.
The parameters that can be modified from the user interface are divided into 3 levels, so as to guarantee maximum security and
user friendliness for less expert users. The display of the parameters depends on the level of password entered; the highest level
password, level 3, allows both the parameters and the passwords to be modified.
The parameters are grouped into screens according to function and the priority. The screens belonging to levels higher than that
accessed by the password entered are not displayed.
/HYHO 'HVFULSWLRQ &RGH
1 Maintenance Man
2 User configuration Cfg1
3 Installer configuration Cfg2
The configuration procedure can be exited by confirming the modifications on the following screen, accessed by pressing the
3UJ button
Update Parameters
Save and exit?
No
Alternatively, the procedure can be exited without confirming the modifications by pressing the (VF button for 3 seconds. The
modifications are also cancelled after 60 seconds of inactivity (no button pressed).
Please remember that any modifications to the configuration corresponding to the network of the connected peripherals, number
of peripherals and type of peripherals, but not the names, automatically deletes the variables log. As a result, if the data saved
needs to be stored, download or print the variables log before making the required modifications.
 /LVWRISDUDPHWHUV
The following list includes all the PlantWatch operating parameters, some of which can be modified only using the 3ODQW:DWFK
PDQDJHUconfiguration program: these are marked by the code PC in the screen code column.
6FUHHQFRGH 'HVFULSWLRQ /HYHO 7\SH 'HIDXOW 0LQ0D[
a1 Buzzer activation time or disabling 2 minutes 1 min disabled
1-20min
continuous
a1 Alarm relay activation time 3 seconds 10 sec disabled
1 sec
20 sec
continuous
a1 Activation of the printer board alarm relay
(Prn relay)
3 flag no
a2 Alarm relay logic, norm. energised/norm
de-energised
3 flag norm de-energ.
a2 Function of second relay 3 flag reset modem Reset modem
Alarms serious
a3 Low freq analogue sampling period 3 minutes 10 min
1 min
120 min
a3 High freq analogue sampling period 3 seconds 10 sec 1 sec
60 sec
a3 Digital sampling period 2 seconds 20 sec 5 sec
300 sec