EasyManua.ls Logo

Carel Power + PSD1 Series - Cooling; Electrical installation

Carel Power + PSD1 Series
48 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
“Power+” +0500048IE - rel 2.2 - 06.11.2014
ENG
Panel installation
80
269,3
M4
Fig. 3.e
Important:
in case of dismantling, do not grab the brackets, but rather the solid“ parts such as the heat sink anche the plastic
cover. Remove the top bracket fi rst, then the bottom one to prevent the drive from falling down.
3.5 Cooling
All the Power+ drives, Coldplate models excluded are fi tted with heatsink and cooling fans. There must be suffi cient
air fl ow and air change inside the electrical panel. Refer to table 5.1 for maximum heat dissipation values.
All the Power+ drives are fi tted with internal cooling fans on the right side. Avoid hot air inlet to internal fan.
≥ 200 mm
≥ 200 mm
≥ 100 mm
Fig. 3.f
3.6 Electrical installation
Important
Important:
before carrying out any maintenance work, disconnect the drive and the external control circuits from the power
supply by moving the main system switch to off . Once power has been disconnected from the drive, wait at least
5 minutes before disconnecting the electrical cables;
always make sure the motor has stopped completely. Motors that are still freely rotating may produce dangerous
voltages at the Power+ terminals, even when this is disconnected from the power supply.

Related product manuals