Refer
to
Tables
4
and
5
for
electrical
data
on
indi¬
vidual
compressors
and
complete
units.
Compressor
usage
is
given
in
Tables
2
and
5.
ELECTRICAL
BOX,
CONTROL
SECTION
Inside
this
section
are
relays,
high-
and
low-
pressure
cutouts,
low
water-temperature
cutout,
timer,
terminal
strips
and
a
3-step
temperature
controller.
On
the
outside
(control
panel)
are
con¬
trol
circuit
ON-OFF
switch,
partial
load
switch
(DLS),
compressor
run
light,
safety
trip
lights
and
control
circuit
fuse.
The
control
panel
is
hinged
to
provide
easy
access
to
the
controls
inside.
^
Table
4
Unit
Voltage
and
Model
Number*
VOLTS
1
...
1
1
UN1T30HK,HL
015,020,025,030
208/230
j
5--
460
6--
_
575
1
1
1--
*Complete
number
has
10
digits.
Example;
30HK020530.
UNBALANCED
3-PHASE
SUPPLY
VOLTAGE
Never
operate
a
motor
where
a
phase
imbalance
in
supply
voltage
is
greater
than
2%.
Use
the
follow¬
ing
formula
to
determine
the
%
voltage
imbalance:
%
Voltage
Imbalance
=
average
voltage
Example:
Supply
voltage
is
240-3-60.
AB
=
243
volts
BC
=
236
volts
AC
==
238
volts
Average
Voltage
=
243
+
236
+
238
3
=
——
-
239
volts
Determine
maximum
deviation
from
average
voltage:
(AB)
243
-
239
=
4
volts
(BC)
239
-
236
=
3
volts
(AC)
239
-
238
=
1
volt
Maximum
deviation
is
4
volts.
Determine
%
voltage
imbalance:
4
%
Voltage
Imbalance
-
100
1T%
This
amount
of
phase
imbalance
is
satisfactory
as
it
is
below
the
maximum
allowable
2%.
IMPGR
PAN
r:
It
the
supply
voltage
phase
im¬
balance
is
more
than
2%^
contact
your
local
electric
utility
company
immediately.
tQUIP
GND
GND-^
TERMINAL
BLOCK
6-POLE
COMPRESSOR
CIRCUIT
BREAKER
(LD-
IL2)-
FIELD
CONTROL
POWER
WIRING
TB2
--T^TBZ
Control
circuit
power
is
from
separate
source,
incoming
wires
are
connected
directly
to
terminals
j
1
j
and
[
2
|
on
TB2
EQUfPGND
Equipment
Ground
Fig.
3
Wiring
Schematic
Unit
and
Control
Power
Supply
ELECTRICAL
BOX,
POWER
SECTION
The
main
electrical
power
supply
is
brought
in
thru
the
top
of
the
electrical
box,
on
the
left-hand
side
(see
Fig.
i).
The
hole
accommodates
up
to
a
3-in.
conduit.
Pressure-lug
connections
on
terminal
block
are
suitable
for
copper,
copper-clad
alumi¬
num
or
aluminum
wire,
unless
otherwise
noted
on
a
label
near
the
terminal
block.
The
power
section
contains:
main
power
terminal
block,
compressor
circuit
breaker
with
calibrated
magnetic
trip
(for
compressor
motor
overload
and
locked
rotor
protection),
and
compressor
motor
contactors.
The
panel
over
this
section
is
secured
with
screws
as
a
safety
measure
against
casual
entry
for
purposes
other
than
service.
5