The
electric
heater
is
wired
into
the
115-volt
control
circuit
thru
normally
closed
contacts
of
control
relay
in
such
a
way
that
it
is
energized
only
when
compressor
is
not
operating.
All
heaters
are
125
watts.
CAU*!
iON:
Never
open
any
switch
or
discon¬
nect
that
will
de-energi/c
ciankca^e
heatci
un¬
less
unit
IS
being
serviced
or
will
be
shut
down
for
a
prolonged
period.
After
such
service
or
prolonged
shutdown,
cnergi/c
crankcase
heater
loi
24
hours
bclore
starting
compressor
TIME
GUARD®
CONTROL
This
control
protects
compressor
against
short
cycling
(Switch
A
on
four-function
timer).
FOUR-FUNCTION
TIMER
Refer
to
Fig.
4
Timer
Cycle.
The
functions
are
as
follows:
Switch
A
(Contacts
A-Al,
A-A2)
runs
timer
motor.
This
provides
a
minimum
of
5-1/2
minutes
after
compressor
stops
before
it
can
restart,
to
prevent
short
cycling
(Time
Guard
control).
Switch
B
(Contacts
B-Bl,
B-B2)
provides
1-second
time
delay
for
part-winding
start
and
also
provides
a
lock-out
function.
Switch
D
(Contacts
D-D
1)
provides
a
2-1
/
2
minute
bypass
of
the
low-pressure
switch
at
start-up
to
prevent
nuisance
trips
under
cold-start
conditions.
Switch
E
(Contacts
E-El)
provides
a
35-second
by¬
pass
of
the
oil
safety
switch
(OPS)
at
compressor
start-up
(when
OPS
is
used),
if
sufficient
oil
pressure
does
not
build
up
in
this
time,
compressor
stops.
SWITCH
POSITION
|
PRESSURE
SETTING
Close
on
rise
i
9
-
1
2
psi
d)ff
1
4
-
6
psi
diff
The
oil
pressure
safety
switch
is
wired
in
parallel
with
Switch
E
of
the
4-function
timer.
This
arrange¬
ment
allows
approximately
35
seconds
for
oil
pres¬
sure
to
reach
normal
operating
level
after
com¬
pressor
starts.
If
the
oil
safety
switch
does
not
close
within
35
seconds,
the
compressor
shuts
down.
To
restart
the
compressor,
the
control
circuit
ON-OFF
switch
must
be
pressed
to
OFF
and
then
to
ON.
The
timer
will
start
and
after
approximately
5-1/2
minutes
compressor
will
start,
if
normal
oil
pressure
is
established
within
the
next
35
seconds,
the
compressor
continues
to
run.
if,
however,
the
oil
pressure
does
not
reach
a
safe
level,
the
compressor
stops
at
the
end
of
the
35
seconds
and
locks
out.
CAUTION:
Do
not
attempt
to
restart
the
com-
prcNSor
lor
a
.second
lime
until
the
pioblem
has
been
determined
and
corrected.
REMOVE
ORANGE
Wl
RE
EE|
7
SEC±4
+-H
1-^5
SEC
DDI
-40SEC15
!
—I
NOTE:
BLACK
DENOTES
CLOSED
CONTACTS
Fig.
4
Timer
Cycle
OIL
PRESSURE
SAFETY
SWITCH
(OPS)
This
control
is
standard
on
30HL
(condenserless)
units
(020-030)
and
is
available
as
an
accessory
for
30HK
units
(020-030).
Refer
to
Fig.
5
for
field
wiring
connections.
It
is
not
available
for
the
015
unit.
The
pressure
switch
is
factory
set
at
the
following
pressures
and
should
not
be
adjusted
in
the
field.
OPS
Oil
Pressure
Safety
Switch
TB
Terminal
Board
Fig.
5
Oil
Pressure
Safety
Switch
to
Control
Box
Wiring
Connections
(020-030
Only)
LOW
LIMIT
STOP
TAB
Fig.
6
Safety
Thermostat
(No.
HH22CC050
Shown)
9
1090