EasyManua.ls Logo

Carrier 30HL - Refrigerant and Oil Handling Procedures; Liquid Charging Method; Adding & Removing Compressor Oil

Carrier 30HL
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The
30HK
units
are
shipped
with
a
full
refrigerant
charge
(see
Table
2).
However,
if
it
is
necessary
to
add
refrigerant,
operate
the
unit
for
some
time
at
full
capacity
and
then
add
charge
until
the
sight
glass
is
clear
of
bubbles.
For
maximum
liquid
subcooling,
liquid
level
should
be
up
to
condenser
liquid
level
test
cock
located
on
shell,
near
condenser
end.
This
usually
requires
additional
refrigerant
charge
beyond
amount
to
clear
sight
glass.
30HL
units
(condenserless)
are
shipped
with
a
holding
charge
only.
After
chiller
assembly
is
com¬
pleted
in
the
field,
system
must
be
fully
charged.
While
unit
is
running
at
full
capacity,
add
refrigerant
until
sight
glass
is
clear.
If
there
is
no
refrigerant
vapor
pressure
in
the
system,
the
entire
system
must
be
leak
tested.
After
repair
of
leaks,
evacuate
system
before
recharging.
See
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Refrigerants,
for
leak
testing,
evacuation
and
charging
procedures.
CAUTION.
When
adjusting
relrigeram
charge,
circulate
water
thru
the
condenser
and
cooler
at
all
times
to
prevent
Iree/ing.
Freezing
damage
is
considered
abuse
and
ma>
allecl
the
Carrier
The
liquid
charging
method
is
recommended
for
complete
charging
or
when
additional
charge
is
required.
LIQUID
CHARGING
METHOD
CAt'
f
ION:
Be
careful
not
to
overcharge
sys¬
tem
Overcharging
results
in
higher
discharge
pressure
with
higher
cooling
water
consump¬
tion.
po.ssible
comprcssoi
damage,
and
higher
iwer
consumption
Charge
thru
1/4-in.
flare
connection
on
liquid
line
shutoff
valve.
Never
charge
liquid
into
low-
pressure
side
oj
system.
1.
Frontseat
(close)
liquid
line
shutoff
valve.
2.
Connect
a
refrigerant
cylinder
loosely
to
charg¬
ing
valve
connection.
Purge
charging
line
and
tighten
connections.
3.
Open
liquid
line
shutoff
valve.
4.
If
system
has
been
dehydrated
and
is
under
vacuum,
break
vacuum
with
refrigerant
(gas
charge).
Build
up
system
pressure
to
58psi
for
R-22
(32
F).
Invert
refrigerant
cylinder
so
that
liquid
refrigerant
will
be
charged.
5.
a.
For
complete
charge,
see
Charging
in
Carrier
Standard
Service
Techniques
Manual,
Chap¬
ter
I,
Refrigerants.
Follow
Charging
By
Weight
procedure.
(When
charge
is
nearly
full,
complete
process
by
observing
sight
glass
for
clear
liquid
flow.)
b.
For
complete
charge
where
refrigerant
cyl¬
inder
cannot
be
weighed,
or
for
adding
refrig¬
erant,
follow
the
procedure
Charging
By
Sight
Glass
in
manual.
6.
T
o
ensure
maximum
subcooler
performance
on
30HK
units,
check
liquid
level
in
condenser
by
means
of
test
cock
located
on
condenser
shell
near
right
end
tube
sheet.
Liquid
discharge
from
test
cock
indicates
fully
charged
subcooler.
Check
Oil
Charge
All
units
are
factory
charged
with
oil.
If
oil
is
visible
in
sight
glass,
check
unit
for
operating
readiness
as
described
in
the
section,
Initial
Check;
then
start
compressor.
Observe
level
and
add
oil,
if
required,
to
bring
level
in
crankcase
1/8
to
3/8
of
bull’s-eye
during
steady
operation.
To
add
or
remove
oil,
see
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Refrigerants.
Use
only
Carrier-approved
compressor
oil:
Witco
Chemical
Co.Suniso
3GS
Texaco,
Inc.
Capella
WF-32
Do
not
reuse
oil
that
has
been
drained
and
do
not
use
oil
that
has
been
exposed
to
atmosphere.
TO
ADD
OIL
Close
suction
shutoff
valve
and
pump
down
crankcase
to
2
psig
(low-pressure
cutout
must
be
bypassed
with
a
jumper).
Wait
a
few
minutes
and
repeat
as
needed
until
pressure
remains
at
2
psig.
Close
discharge
shutoff
valve.
Remove
oil
fill
plug
above
bull’s-eye,
add
oil
thru
plug
hole
and
replace
plug.
Reopen
suction
and
discharge
valves.
Run
compressor
for
about
20
minutes
and
check
oil
level.
TO
REMOVE
OIL
Pump
down
compressor
to
2
psig.
Close
suction
and
discharge
valves.
Loosen
the
1/
4-in.
pipe
plug
in
compressor
base
and
allow
oil
to
seep
out
past
plug
threads.
The
crankcase
will
be
under
slight
pressure.
Be
careful
not
to
remove
plug;
the
entire
oil
charge
may
be
lost.
Small
amounts
of
oil
can
be
removed
thru
oil
pump
discharge
connection
while
compressor
is
running.
START-UP
Start-up
should
be
performed
only
under
super¬
vision
of
experienced
refrigeration
mechanic.
Be
sure
crankcase
heaters
have
been
energized
for
24
hours.
!.
Open
all
system
valves
that
may
have
been
closed
during
or
after
charging.
2.
Check
air
handling
equipment,
chilled
water
and
condenser
water
pumps,
and
any
other
equip¬
ment
connected
to
chiller.
3.
Start
unit
by
firmly
pushing
ON
button.
4.
Check
all
controls
for
proper
operation.
Refer
to
Check
Unit
Safety
Devices.
5.
Adjust
water-regulating
valve
(if
used)
to
most
economical
head
pressure
(based
on
relative
cost
of
water
and
electricity).
Head
pressure
is
nor¬
mally
200
to
230
psi
for
R-22.
7
1090

Related product manuals