EasyManua.ls Logo

Carrier 30HL - Refrigerant System Components; Compressor Protection Devices

Carrier 30HL
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.
Check
leaving
chilled
water
temperature
to
see
that
it
remains
well
above
freezing.
7.
Recheck
compressor
oil
level.
See
Check
Oil
Charge.
Check
Refrigerant
Feed
Components
THERMOSTATIC
EXPANSION
VALVE
(TXV)
This
valve
controls
refrigerant
flow.
Valve
is
activated
by
a
temperature
sensing
bulb
clamped
to
suction
line.
The
valve
is
factory
set
to
maintain
a
superheat
of
8
F
to
10
F.
Do
nol
change
setting
unless
absolutely
necessary.
FILTER
DRIER
The
30HK,HL015
thru
030
units
(single
com¬
pressor)
have
sealed-type
driers.
When
a
drier
must
be
changed,
the
entire
drier
must
be
replaced.
The
function
of
the
filter
drier
is
to
maintain
a
clean,
dry
system.
The
moisture
indicator
(below)
can
indi¬
cate
any
need
to
change
filter
drier.
MOISTURE-LIQUID
INDICATOR
The
indicator
is
located
immediately
ahead
of
the
TXV
to
provide
a
constant
indication
of
refrig¬
erant
moisture
content.
It
also
provides
a
sight
glass
for
refrigerant
liquid.
Clear
flow
of
liquid
refrigerant
indicates
sufficient
charge
in
system.
Bubbles
indicate
under-charged
system
or
presence
of
noncondensables.
Moisture
in
the
system,
measured
in
parts
per
million
(ppm),
will
change
color
of
indicator.
Unit
must
be
in
operation
at
least
12
hours
before
moisture
indicator
will
give
an
accurate
reading.
With
unit
running,
indicating
element
must
be
in
contact
with
liquid
refrigerant
to
give
true
moisture
indication.
At
first
sign
of
moisture
in
the
system,
change
the
filter
drier.
The
tables
below
indicate
when
the
change
is
required.
30HK,HL01
5,020
COLOR
CONDITION
Green
Dry;
moisture
is
below
45
ppm
Chartreuse
Caution:
45
ppm
Yellow
Wet:
above
130
ppm
30HK,HL025,030
COLOR
CONDITION
Blue
:
Safe,
dry
Light
violet
First
sign
of
moisture
Pink
i
Dangerous
moisture
level
LIQUID-LINE
SERVICE
VALVE
This
valve
provides
a
refrigerant
charging
port
and,
in
combination
with
the
compressor
discharge
service
valve,
allows
the
refrigerant
to
be
pumped
into
the
high
side.
LIQUID-LINE
SOLENOID
VALVE
(HL
only)
The
solenoid
valve
closes
when
its
circuit
is
in¬
operative,
either
from
capacity
control
or
from
any
safety
trip.
PRESSURE
RELIEF
DEVICES
On
HK
units,
a
high-side
pressure-relief
valve
is
factory
installed
on
the
condenser.
The
valve
is
set
to
open
at
a
maximum
pressure
of
385
psig
(maxi¬
mum
design
working
pressure
of
the
condenser).
For
30HL
units,
pressure
relief
device,
designed
to
relieve
at
450
psig,
is
field
supplied
and
installed
in
the
discharge
line
after
the
muffler
according
to
ANSI.B9.1
code
requirements.
Additional
pressure
relief
valves,
properly
se¬
lected,
must
be
field
installed
to
protect
field-
installed
high-side
equipment
as
may
be
required
by
applicable
codes.
A
fusible
plug
is
factory
installed
on
the
suction
line
for
low-side
protection.
This
plug
will
relieve
on
temperature
rise
to
170F.
Most
local
codes
require
that
a
relief
valve
be
vented
directly
to
outdoors.
The
vent
line
must
not
be
smaller
than
the
relief
valve
outlet
(5i8-in.
SAE).
CHECK
VALVE
A
discharge-line
check
valve
is
supplied
with
each
condenseriess
(HL)
unit
as
standard
equipment.
This
valve
should
be
located
downstream
from,
but
close
to,
the
hot
gas
muffler.
The
valve
can
be
mounted
in
either
horizontal
or
vertical
position.
The
valve
prevents
migration
of
refrigerant
from
condenser
to
compressor
and
cooler
during
off-
cycle
of
compressor.
Check
Compressor
Protection
Devices
CIRCUIT
BREAKER
The
compressor
is
protected
against
an
over¬
current
condition
by
a
manual-reset
calibrated-trip
circuit
breaker.
MOTOR
OVERTEMPERATURE
THERMOSTAT
On
size
015
units,
a
sensor
embedded
in
motor
windings
protects
against
overtemperature.
On
all
other
sizes,
a
sensor
in
the
discharge
side
of
the
compressor
reacts
to
excessively
high
dis¬
charge
gas
temperature
and
shuts
off
the
com¬
pressor.
A
high
discharge
gas
temperature
indicates
an
overtemperature
condition
in
motor
windings.
CRANKCASE
HEATER
The
heater
prevents
absorption
of
liquid
refrig¬
erant
by
oil
when
compressor
is
not
operating.
On
size
015
units,
the
heater
is
secured
by
a
clip;
on
all
other
sizes,
it
is
held
in
place
by
a
bracket.
CAU'i
iON:
The
heater
must
be
light
to
prevent
it
from
backing
out
of
the
crankcase,
i
he
heater
will
burn
out
if
exposed
to
air
for
an
extended
1090
8

Related product manuals