Table 25—Indoor Unit Error Display
OPERATION
LAMP
TIMER LAMP DISPLAY LED STATUS
1time
X E0 Indoor unit EEPROM error
2times X E1 Communication malfunction between indoor and outdoor units.
4times X E3 Indoor fan speed has been out of control
5times X E4 Indoor room temperature sensor T1 open circuit or short circuit
6times X E5 Evaporator coil temperature sensor T2 open circuit or short circuit
7times X EC Refrigerant leakage detection
8times X EE Water --- level alarm malfunction
1time O F0 Current overload protection
2times O F1 Open circuit or short circuit of outdoor ambient temperature sensor T4
3times O F2 Open circuit or short circuit of condenser coil temperature sensor T3
4times O F3 Open circuit or short circuit of Compressor discharge temperature sensor T5
5times O F4 Outdoor unit EEPROM error
6times O F5 Outdoor fan speed has been out of control
7times O F6 T2B sensor error
8times O F7 Lifting---panel communication error
9times O F8 Lifting--- panel malfunction
10 times O F9 Lifting--- panel is not closed
1time P0 IPM malfunction
2times P1 Over voltage or over low voltage protection
3times P2 High temperature protection of compressor top
4times P3 Outdoor low temperature protection
5times P4 Inverter compressor drive error
6times P5 Mode conflict
7times P6 Compressor low--- pressure protection
8times P7 Outdoor IGBT temperature sensor error
O (light) X (off) (flash)
OUTDOOR UNIT DIAGNOSTIC GUIDES
This unit has on--board diagnostics. Error codes are displayed on the wired remote controller and the outdoor unit microprocessor board with
colored LED lights. The table below explains the error codes on both.
Table 26—Outdoor Unit Error Display
DISPLAY LED STATUS IDU E rror IDU Error
E0 Outdoor EEPROM malfunction F4 E6
E2 Communication malfunction between indoor and outdoor units E1 E2
E3 Communication malfunction between IPM board and outdoor main board —— ——
E4 Open or short circuit of outdoor temperature sensor (T3T4T5T2B) F2 E6
E5 Voltage protection P1 P0
E6 PFC module protection —— ——
E8 Outdoor fan speed has been out of control (Only for DC fan motor models) F5 ——
E9 Wrong wiring connection of 24K indoor unit —— ——
F1 No A Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F2 No B Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F3 No C Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F4 No D Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F5 No E Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F6 No F Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
P0 Temperature protection of compressor top P2 P3(P1)
P1 High pressure protection —— ——
P2 Low pressure protection —— ——
P3 Current protection of compressor —— ——(P2)
P4 Temperature protection of compressor discharge —— ——
P5 High temperature protection of condenser —— ——
P6 IPM module protection P0 E5