50 Specifications subject to change without notice. 38MGR-04SM
DIAGNOSIS AND SOLUTION (CONT)
Outdoor fan speed has been out of control (E8)
Troubleshooting
ERROR CODE E8
MALFUNCTION DECISION
CONDITIONS
When the outdoor fan speed stays too low (300RPM) or too high (2400RPM) for certain time, the unit
stops and the LED displays the failure.
SUPPOSED CAUSES
Wiring mistake
Fan assembly faulty
Fan motor faulty
PCB faulty
No
Yes
No
No
Yes
Yes
No
Yes
No
Power o, then restart the unit
3 minutes later.
Is it still displaying the error code?
The unit operates normally.
Shut o the power supply,
rotate the fan by hand.
Does it rotate properly?
Determine the cause and
resolve it.
For example, if the fan is
blocked or the screws
which secure the fan
are tightened.
Check the fan motor wiring.
Are all of the connections good?
Correct the connections.
Check whether the main PCB is
normal (see Index 1).
Replace the main PCB.
Replace the fan motor.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 38MGRQ24C 3 Series and is the answer not in the manual?

Carrier 38MGRQ24C 3 Series Specifications

General IconGeneral
BrandCarrier
Model38MGRQ24C 3 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals