Table 2 Electric Heater Data for Units with PSC Motor (cont)
LEGEND
*Left hand coil connections only.
NOTES:
1. LAT (Leaving Air Temperature)(F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER
OF
ELEMENTS
FLA
LAT
(F)
MCA MOCP
TOTAL
CAPACITY
(kW)
40UV,UH125
(at 1250 Cfm)
1
/
5
208/1/60
3 38.1 89 47.6 50 7.5
4 50.1 96 62.7 70 10.0
5 62.2 102 77.7 80 12.5
6 74.2 108 92.8 100 15.0
240/1/60
3 43.7 96 54.6 60 10.0
4 57.6 104 71.9 80 13.3
5 71.4 113 89.3 90 16.7
6* 85.3 121 106.7 110 20.0
277/1/60
3 37.7 96 47.1 50 10.0
4 49.7 104 62.2 70 13.3
5 61.8 113 77.2 80 16.7
6 73.8 121 92.2 100 20.0
208/3/60
3 22.9 89 28.6 30 7.5
4 34.9 96 43.6 45 10.0
5 43.7 102 54.7 60 12.5
6 43.7 108 54.7 60 15.0
240/3/60
3 26.1 96 32.6 35 10.0
4 40.0 104 50.0 50 13.3
5 50.2 113 62.7 70 16.7
6 50.2 121 62.7 70 20.0
460/3/60
3 13.0 96 16.2 20 10.0
4 19.9 104 24.9 25 13.3
5 25.0 113 31.3 35 16.7
6 25.0 121 31.3 35 20.0
DX Direct Expansion
FLA Full Load Amps
LAT Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA Unit Minimum Circuit Ampacity
MOCP Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC Permanent Split Capacitor