EasyManua.ls Logo

Carrier 40UV - Page 13

Carrier 40UV
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Table 2 Electric Heater Data for Units with PSC Motor (cont)
LEGEND
*Left hand coil connections only.
NOTES:
1. LAT (Leaving Air Temperature)(F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER
OF
ELEMENTS
FLA
LAT
(F)
MCA MOCP
TOTAL
CAPACITY
(kW)
40UV,UH150
(at 1500 Cfm)
1
/
5
208/1/60
3 45.3 89 56.7 60 9.0
4 59.8 96 74.7 80 12.0
5 74.2 102 92.8 100 15.0
6* 88.7 108 110.8 125 18.0
240/1/60
3 52.0 96 65.0 70 12.0
4 68.7 104 85.8 90 16.0
5* 85.3 113 106.7 110 20.0
6 —————
277/1/60
3 44.9 96 56.2 60 12.0
4 59.4 104 74.2 80 16.0
5 73.8 113 92.3 100 20.0
6 —————
208/3/60
3 27.0 89 33.8 35 9.0
4 41.5 96 51.9 60 12.0
5 52.1 102 65.1 70 15.0
6 52.1 108 65.1 70 18.0
240/3/60
3 30.9 96 38.6 40 12.0
4 47.6 104 59.5 60 16.0
5 59.8 113 74.8 80 20.0
6 59.8 121 74.8 80 24.0
460/3/60
3 15.4 96 19.2 20 12.0
4 23.7 104 29.6 30 16.0
5 29.8 113 37.3 40 20.0
6 29.8 121 37.3 40 24.0
DX Direct Expansion
FLA Full Load Amps
LAT Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA Unit Minimum Circuit Ampacity
MOCP Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC Permanent Split Capacitor

Table of Contents

Other manuals for Carrier 40UV

Related product manuals