Table 3 Electric Heater Data for Units with ECM
LEGEND NOTES:
1. LAT (Leaving Air Temperature)(F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER
OF
ELEMENTS
FLA
LAT
(F)
MCA MOCP
TOTAL
CAPACITY
(kW)
40UV050
(at 500 Cfm)
1
/
3
208/1/60
3 16.5 90 20.6 25 3.2
4 21.5 97 26.9 30 4.2
5 26.6 104 33.2 35 5.3
6 31.6 110 39.5 40 6.3
240/1/60
3 18.8 97 23.5 25 4.2
4 24.6 106 30.8 35 5.6
5 30.5 115 38.1 40 7.0
6 36.3 124 45.4 50 8.4
277/1/60
3 16.3 97 20.3 25 4.2
4 21.3 106 26.6 30 5.6
5 26.4 115 33.0 35 7.0
6 31.4 124 39.3 40 8.4
208/3/60
3 10.1 90 12.6 15 3.2
4 15.1 97 18.9 20 4.2
5 18.8 104 23.5 25 5.3
6 18.8 110 23.5 25 6.3
240/3/60
3 11.4 97 14.3 15 4.2
4 17.2 106 21.6 25 5.6
5 21.5 115 26.9 30 7.0
6 21.5 124 26.9 30 8.4
460/3/60
3 5.4 97 6.8 15 4.2
4 8.3 106 10.4 15 5.6
5 10.5 115 13.1 15 7.0
6 10.5 124 13.1 15 8.4
DX Direct Expansion
FLA Full Load Amps
LAT Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA Unit Minimum Circuit Ampacity
MOCP Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC Permanent Split Capacitor