15
Table 3 — Electric Heater Data for Units with ECM (cont)
LEGEND NOTES:
1. LAT (Leaving Air Temperature)(F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER
OF
ELEMENTS
FLA
LAT
(F)
MCA MOCP
TOTAL
CAPACITY
(kW)
40UV,UH075
(at 750 Cfm)
1
/
3
208/1/60
3 24.0 89 30.0 30 4.5
4 31.2 96 39.0 40 6.0
5 38.4 102 48.0 50 7.5
6 45.6 108 57.0 60 9.0
240/1/60
3 27.3 96 34.1 35 6.0
4 35.6 104 44.5 45 8.0
5 44.0 113 55.0 60 10.0
6 52.3 121 65.4 70 12.0
277/1/60
3 23.7 96 29.6 30 6.0
4 30.9 104 38.6 40 8.0
5 38.1 113 47.6 50 10.0
6 45.3 121 56.7 60 12.0
208/3/60
3 14.8 89 18.5 20 4.5
4 22.0 96 27.6 30 6.0
5 27.3 102 34.2 35 7.5
6 27.3 108 34.2 35 9.0
240/3/60
3 16.8 96 20.9 25 6.0
4 25.1 104 31.4 35 8.0
5 31.2 113 39.0 40 10.0
6 31.2 121 39.0 40 12.0
460/3/60
3 8.2 96 10.2 15 6.0
4 12.3 104 15.4 20 8.0
5 15.4 113 19.2 20 10.0
6 15.4 121 19.2 20 12.0
DX — Direct Expansion
FLA — Full Load Amps
LAT — Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA — Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC — Permanent Split Capacitor