Table 3 Electric Heater Data for Units with ECM (cont)
LEGEND
*Left hand coil connections only.
NOTES:
1. LAT (Leaving Air Temperature)(F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER
OF
ELEMENTS
FLA
LAT
(F)
MCA MOCP
TOTAL
CAPACITY
(kW)
40UV,UH125
(at 1250 Cfm)
1
/
2
208/1/60
3 39.4 89 49.3 50 7.5
4 51.5 96 64.3 70 10.0
5 63.5 102 79.4 80 12.5
6 75.5 108 94.4 100 15.0
240/1/60
3 45.0 96 56.2 60 10.0
4 58.9 104 73.6 80 13.3
5 72.7 113 90.9 100 16.7
6* 86.6 121 108.3 110 20.0
277/1/60
3 39.0 96 48.7 50 10.0
4 51.0 104 63.8 70 13.3
5 63.1 113 78.8 80 16.7
6 75.1 121 93.9 100 20.0
208/3/60
3 24.2 89 30.2 35 7.5
4 36.2 96 45.3 50 10.0
5 45.0 102 56.3 60 12.5
6 45.0 108 56.3 60 15.0
240/3/60
3 27.4 96 34.2 35 10.0
4 41.3 104 51.6 60 13.3
5 51.5 113 64.3 70 16.7
6 51.5 121 64.3 70 20.0
460/3/60
3 13.2 96 16.5 20 10.0
4 20.2 104 25.2 30 13.3
5 25.3 113 31.6 35 16.7
6 25.3 121 31.6 35 20.0
DX Direct Expansion
FLA Full Load Amps
LAT Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA Unit Minimum Circuit Ampacity
MOCP Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC Permanent Split Capacitor