EasyManua.ls Logo

Carrier 40UV - Page 18

Carrier 40UV
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
Table 3 Electric Heater Data for Units with ECM (cont)
LEGEND
*Left hand coil connections only.
NOTES:
1. LAT (Leaving Air Temperature)(F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER
OF
ELEMENTS
FLA
LAT
(F)
MCA MOCP
TOTAL
CAPACITY
(kW)
40UV,UH150
(at 1500 Cfm)
1
/
2
208/1/60
3 46.7 89 58.3 60 9.0
4 61.1 96 76.4 80 12.0
5 75.6 102 94.4 100 15.0
6* 90.0 108 112.5 125 18.0
240/1/60
3 53.3 96 66.6 70 12.0
4 70.0 104 87.5 90 16.0
5* 86.6 113 108.3 110 20.0
6 —————
277/1/60
3 46.2 96 57.8 60 12.0
4 60.7 104 75.8 80 16.0
5 75.1 113 93.9 100 20.0
6 —————
208/3/60
3 28.3 89 35.4 40 9.0
4 42.8 96 53.5 60 12.0
5 53.4 102 66.7 70 15.0
6 53.4 108 66.7 70 18.0
240/3/60
3 32.2 96 40.3 45 12.0
4 48.9 104 61.1 70 16.0
5 61.1 113 76.4 80 20.0
6 61.1 121 76.4 80 24.0
460/3/60
3 15.6 96 19.5 20 12.0
4 24.0 104 30.0 30 16.0
5 30.1 113 37.6 40 20.0
6 30.1 121 37.6 40 24.0
DX Direct Expansion
FLA Full Load Amps
LAT Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA Unit Minimum Circuit Ampacity
MOCP Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC Permanent Split Capacitor

Table of Contents

Other manuals for Carrier 40UV

Related product manuals