Table 3 Electric Heater Data for Units with ECM (cont)
LEGEND
*Left hand coil connections only.
NOTES:
1. LAT (Leaving Air Temperature)(F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER
OF
ELEMENTS
FLA
LAT
(F)
MCA MOCP
TOTAL
CAPACITY
(kW)
40UH200
(at 2000 Cfm)
3
/
4
208/1/60
3 50.1 84 62.7 70 9.0
4 64.6 89 80.7 90 12.0
5 79.0 94 98.8 100 15.0
6* 93.5 99 116.8 125 18.0
240/1/60
3 56.8 89 71.0 80 12.0
4 73.5 96 91.8 100 16.0
5* 90.1 102 112.7 125 20.0
6 —————
277/1/60
3 48.8 89 61.0 70 12.0
4 63.3 96 79.1 80 16.0
5 77.7 102 97.1 100 20.0
6 —————
208/3/60
3 31.8 84 39.8 40 9.0
4 46.3 89 57.9 60 12.0
5 56.9 94 71.1 80 15.0
6 56.9 99 71.1 80 18.0
240/3/60
3 35.7 89 44.6 45 12.0
4 52.4 96 65.5 70 16.0
5 64.6 102 80.8 90 20.0
6 64.6 108 80.8 90 24.0
460/3/60
3 16.9 89 21.1 25 12.0
4 25.2 96 31.5 35 16.0
5 31.3 102 39.1 40 20.0
6 31.3 108 39.1 40 24.0
DX Direct Expansion
FLA Full Load Amps
LAT Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA Unit Minimum Circuit Ampacity
MOCP Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC Permanent Split Capacitor