heating performance is not required. The standard ther-
mostat control option is line voltage except on 42SU and
42SM, which include a low voltage control package as
standard. Unit-mounted line voltage and 24-v thermostats
are available on the 42V Series units. For thermostat con-
trol package options refer to pages 13-16.
42C SEISMIC COMPLIANCE OPTION COMPATIBILITY CHART
OPTION DESCRIPTION
UNIT
42CA 42CE 42CG 42CK
2-Pipe Hydronic Coil
Configurations
2-Row Coil I I I/O I/O
3-Row Coil I I I/O I/O
4-Row or 5-Row Coil I I I/O I/O
4-Pipe Hydronic Coil
Configuration
2/1 or 2/2 Split Coil I I I/O I/O
3/1, 3/2, or 4/1 Split Coil I I I/O I/O
Electric Heat All electric heat options I I I/O I/O
Service Switches All service switch options I I I/O I/O
Coil Options
Stainless steel coil wrapper I I I/O I/O
Coil air vents (manual or automatic) I I I/O I/O
Coil drains I I I/O I/O
PSC Motors 115V, 208V, 230V, 277V, Single Phase, 60 Hz I I I/O I/O
Control Packages
All control package options EXCEPT Fan Coil
Open and CCN Controllers (Digit 16 cannot be
W or Z)
III/OI/O
Individual Valves and
Valve Packages
All valve options EXCEPT modulating valves and
valve packages containing modulating valves
III/OI/O
Filters
1-inch throwaway or permanent washable NA I I/O I/O
1-inch pleated MERV 8 NA I I/O I/O
Drain Pan
Standard drain pan I I I/O I/O
Stainless steel drain pan I I I/O I/O
Tell-Tale I I I/O I/O
Drip Lip I I I/O I/O
Extended main drain pan (galvanized or stain-
less steel)
III/OI/O
Condensate overflow switch (option 26-A) I I I/O I/O
Cabinet Insulation
Standard Tuf-Skin fiberglass insulation I I I/O I/O
Foil-faced fiberglass insulation I I I/O I/O
LEGEND
I — International Building Code (IBC) Compliance
O — Office of Statewide Health Planning and Development (OSHPD)
Pre-Approved (OSP-0229-10)
NOTES:
1. Seismic compliance option includes factory-supplied, field-
installed isolation hanger and seismic restraints required for a
given unit.
2. Direct expansion (DX) coils and steam coils are not compatible
with seismic compliance option.
3. Electonically commutated motors (ECM) are not compatible with
seismic compliance option.

Other manuals for Carrier 42C Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 42C Series and is the answer not in the manual?

Carrier 42C Series Specifications

General IconGeneral
BrandCarrier
Model42C Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals