APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)
(IN ALPHABETICAL ORDER)
BACnet Modbus N2 LON Works
Point Name
Read/
Write
BACnet Point
Name
OBJECT
ID
Register
Typ e
Register
#
Network
Point
Typ e
Network
Point
Address
SNVT Type SNVT Name
Input 1 Function
R/W
ai1_function
MSV:8100
1
Input 2 Function
R/W
ai2_function
MSV:8100
2
Input 3 Function
R/W
di3_function
MSV:8100
3
Input 3 Switch Con-
figuration
R/W
di3_type
MSV:8101
3
Input 5 Function
R/W
di5_function
MSV:8100
5
Input 5 Switch Con-
figuration
R/W
di5_type
MSV:8101
5
Input 8 Function
R/W
di8_function
MSV:8100
8
Input 8 Switch Con-
figuration
R/W
di8_type
MSV:8101
8
Input 9 Function
R/W
di9_function
MSV:8100
9
Input 9 Switch Con-
figuration
R/W
di9_type
MSV:8101
9
input_1 R ai_1 AI:1001
input_10 R ai_10 AI:1010
input_11 R ai_11 AI:1011
input_2 R ai_2 AI:1002
input_3 R di_3 BI:1003
input_4 R di_4 BI:1004
input_5 R di_5 BI:1005
input_7 R ai_7 AI:1007
input_8 R di_8 BI:1008
input_9 R di_9 BI:1009
Low Space Relative
Humidity
R
sprh_l o_ alarm BV:7019
discrete
in
10038 BI 38
SNVT_switch
(95)
nvoLoS-
PRHAlm
Low Space Temp
Alarm
R
spt_lo_alarm BV:7012
discrete
in
10039 BI 39
SNVT_switch
(95)
nvo-
LoSpaceTemp
Low Supply Air Tem-
perature
R
sat_lo_alarm BV:7021
discrete
in
10040 BI 40
SNVT_switch
(95)
nvoLoSATAlm
Maximum Heating
SAT
R/W
sat_ht_max AV:83004
Min Setpoint S epara-
tion
R/W
min_stpt_sep AV:63
Minimum C ooling
SAT
R/W
sat_cl_min AV:83003
OAQ Sensor
R
oaq_alarm BV:7006
discrete
in
10041 BI 41
SNVT_switch
(95)
nvoOAQSens
or
Occ Relative Humid-
ity Setpoint
R/W
occ_de-
hum_stpt
AV:3011
float
valu e
40083 ADF 36
SNVT_lev_per-
cent (81)
nviOccRHSP
Occupancy Contact
R
occ_con-
tact_status
BV:1007
Occupancy Source R/W occ_source MSV:1002
Occupancy Status
R
occ_status BV:2008
discrete
in
10018 BI 18
SNVT_switch
(95)
nvoOccStatus
Operating Mode
R
run_status MSV:2002
un-
signed
int
30001 ADI 13
SNVT_count_inc
(9)
nvoOperating-
Mode
Optimal Start
R/W
optm_start AV:9026
float
valu e
40147 ADF 61
SN-
VT_time_hour
(124)
nviOptimal-
Start
Outdoor Air CO2
R
oaq AV:1010
float
valu e
40085 ADF 37 SNVT_ppm (29) nvoOAQ
Outdoor Air Temp
Sensor Alarm
R
oat_alarm BV:7003
Outdoor Air Temper-
ature
R
oa_temp AV:1003
float
valu e
40087 ADF 38
SNVT_temp_p
(105)
nvoOAT
Outdoor C O2 Sensor
Value @ Max mA
R/W
oaq_ref_hi_pp
m
AV:9014
Outdoor C O2 Sensor
Value @ Min mA
R/W
oaq_ref_lo_pp
m
AV:9013