RTU--OPEN START--UP SHEET
RTU Model Number: Date:
RTU Serial Number:
Performed by:
RTU--- OPEN Software Version: Company:
Protocol and Boad Rate: Network Address:
CONFIGURATION POINTS
BACview
MENU
POINT NAME
BACnet
OBJECT
RANGE DEFAULT ENTRY
HOME Select function below
CONFIG CONFIGURATION
SET-
POINT
SETPOINTS
Occupied Heating Setpoint occ_ht_stpt 40--- 90 ° F 70
Occupied Cooling Setpoint occ_cl_stpt 55---99 ° F 74
Unoccupied Heating Setpoint unocc_ht_stpt 40---90 ° F 55
Unoccupied Cooling Setpoint unocc_cl_stpt 55---99 ° F 90
Effective Cool Setpoint eff_cl_stpt xx ° F
Effective Heat Setpoint eff_ht_stpt xx ° F
Optimal Start optm_start 0 --- 4 h r 4
Occ Relative Humidity Setpoint occ_dehum_stpt 0--- unocc setpoint
%rh
60
Unocc Relative Humidity Setpoint unocc_de-
hum_stpt
30---100 %rh 95
DCV Max Ctrl Setpoint iaq_stpt_max 0---9999 ppm 650
Power Exhaust Setpoint pexh_stpt 20--- 90 %Open 50
ALARMS
ALARM CONFIGURATION
SPACE T EMPERATURE ALARM
Occupied Alarm Hysteresis occ_spt_alrm_hyst 2 --- 2 0 ° F 3
Alarm Delay (min/deg) spt_alrm_delay 0 --- 3 0 m i n u t e s 10
Unoccupied Low SPT Alarm Limit uno_spt_alrm_lo_l
mt
35---90 ° F 45
Unoccupied High SPT Alarm Limit uno_spt_alrm_hi_l
mt
45---100 ° F 95
SUPPLY AIR TEMPERATURE ALARM
Low SAT Alarm Limit sat_lo_alrm_lim 15---90 ° F 35
High SAT Alarm Limit sat_hi_alrm_lim 90--- 175 ° F 160
SP ACE HUMIDITY ALARM
Low Space Humidity Alarm Limit sprh_lo_alrm_lim 0 --- 9 9 % r h 30
High Space Humidity Alarm Limit sprh_hi_alrm_lim 0 --- 9 9 % r h 70
IAQ / VENTILATION ALARM
Occ High CO2 Alarm Limit (ppm) iaq_occ_hi_lmt 0---9999 ppm 1200