CONFIGURATION POINTS (CON’T)
BACview
MENU
POINT NAME
BACnet
OBJECT
RANGE DEFAULT ENTRY
HOME Select function below
CONFIG CONFIGURATION
UNIT
UNIT CONFIGURATION
Fan Mode fan_mode 1=Auto
2=Continuous
3=Always On
Continuous
Unit Start Delay start_delay 0 --- 3 0 s e c 5
Fan Off Delay fan_delay_off 0 --- 1 8 0 s e c 90
Minimum Cooling SAT sat_cl_min 45--- 75 ° F 50
Maximum Heating SAT sat_ht_max 95---150° F 120
Vent Dmpr Pos / DCV Min P os econ_min 0 --- 1 0 0 % O p e n 20
DCV Max Vent Damper P os iaq_dpr_max 10---60 %Open 50
S Fan Service Alarm Timer sfan_service_hrs 0---9999 hr 0
Comp 1 Service Alarm Timer comp1_ser-
vice_hrs
0---9999 hr 0
Comp 2 Service Alarm Timer comp2_ser-
vice_hrs
0---9999 hr 0
Filter Service Alarm Timer filter_service_hrs 0--- 9999 hr 600
Pushbutton Override pb_enable Disable/Enable Enable
Setpoint Adjustment stpt_adj_enable Disable/Enable Enable
Setpoint Adjustment Range stpt_adj_range + / --- 0 --- 5 ° F 5
Cooling Lockout Temperature oat_cl_lockout 0 --- 8 0 ° F 45
Economizer High OAT Lockout Temp oat_ec_lockout 55--- 80° F 75
HP Rev Cycle Lockout Temp hp_rev_cycle_lock-
out
--- 2 0 --- 3 0 ° F --- 3
Heating Lockout Temperature oat_ht_lockout 35--- 150° F 65
Unocc Free Cool Enable ntfc_ena Disable/Enable Disable
Setpoint Separation min_stpt_sep 2 --- 1 0 ° F 5
Occupancy Source occ_source 1=Always occupied
2=BACnet Sched-
ule
3=BAS On/Off
4=Remote Occ In-
put
Always Occupied
CAL-
IBRATE
SENSOR CALIBRATION
Space Temp Calibration spt_offset --- 9 . 9 --- 1 0 ° F 0
Supply Air Temp Calibration sat_offset --- 9 . 9 --- 1 0 ° F 0
Outdoor Air Temp Calibration oat_offset --- 9 . 9 --- 1 0 ° F 0