43
CONFIGURATION POINTS (CON’T)
BACview
MENU
POINT NAME
BACnet
OBJECT
RANGE DEFAULT ENTRY
HOME Select function below
CONFIG CONFIGURATION
INPUT
INPUT CONFIGURATION
Input 1 Function ai1_function 1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH
Sensor
No Sensor
Input 2 Function ai2_function 1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH
Sensor
1(NoFIOP)
2(FIOP)
Input 3 Function di3_function 1=No Function
2=Compressor
Safety
3=Fan Status
4=Filter Status
5=Remote Occu-
pancy
6=Door Contact
Compressor Safety
Input 3 Switch Configuration di3_type N/O
N/C
N/O
Input 5 Function di5_function 1=No Function
2=Fire Shutdown
3=Fan Status
4=Filter Status
5=Remote Occu-
pancy
6=Door Contact
Fire Shutdown
Input 5 Switch Configuration di5_type N/O
N/C
N/O
Input 8 Function di8_function 1=No Function
2=Enthalpy Switch
3=Fan Status
4=Filter Status
5=Remote Occu-
pancy
6=Door Contact
1(NoFIOP)
2(FIOP)
Input 8 Switch Configuration di8_type N/O
N/C
N/O
Input 9 Function di9_function 1=No Function
2=Humidistat
3=Fan Status
4=Filter Status
5=Remote Occu-
pancy
6=Door Contact
Humidistat
Input 9 Switch Configuration di9_type N/O
N/C
N/O
Space sensor type spt_type 1=T55
2=T56 (use for T59)
3=SPT Sensor
T55
T5x Override Duration ovr_dur 0---24 hours 1