NOTE: Some parameters in the menus use the letters MA or
MAT, indicating a mixed air temperature sensor location before
the cooling coil. This unit application has the control sensor locat-
ed after the cooling coil, in the fan section, where it is designated
as (Cooling) Supply Air Temperature or SAT sensor.
Setup and Configuration
Before being placed into service, the W7220 economizer module
must be setup and configured for the installed system.
The setup process uses a hierarchical menu structure that is easy to
use. Press the and arrow buttons to move forward and back-
ward through the menus and press the button to select and confirm
setup item changes.
Time-out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD
displays a screen saver, which cycles through the Status items.
Each Status items displays in turn and cycles to the next item
after 5 seconds.
IMPORTANT: Table 19 illustrates the complete hierarchy.
Your menu parameters may be different depending on
your configuration.
For example, if you do not have a DCV (CO
2
) sensor, then
none of the DCV parameters appear and only MIN POS will
display. If you have a CO
2
sensor, the DCV MIN and DCV
MAX will appear AND if you have 2 speed fan DCV MIN
(high and low speed) and DCV MAX (high and low speed
will appear).
IMPORTANT: During setup, the economizer module is live
at all times.
Table 19 — W7220 Menu Structure
a
MENU PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
b
NOTES
STATUS
ECONO AVAIL NO YES/NO
FIRST STAGE COOLING DEMAND (Y1–IN)
YES = economizing available; the system can use outside air for free
cooling when required
ECONOMIZING NO YES/NO
FIRST STAGE COOLING RELAY OUTPUT
YES = outside air being used for 1 stage cooling
OCCUPIED
c
NO YES/NO
OCCUPIED
YES = OCC signal received from space thermostat or unitary controller
YES = 24 vac on terminal OCC
NO = 0 vac on terminal OCC
HEAT PUMP N/A
d
COOL
HEAT
HEAT PUMP MODE
Displays COOL or HEAT when system is set to heat pump
(Non-conventional)
COOL Y1—IN OFF ON/OFF
FIRST STAGE COOLING DEMAND (Y1-IN)
Y1–I signal from space thermostat or unitary controller for cooling
stage 1.
ON = 24 vac on terminal Y1–I
OFF = 0 vac on terminal Y1–I
COOL Y1—OUT OFF ON/OFF
FIRST STAGE COOLING RELAY OUTPUT
Cool stage 1 Relay Output to stage 1 mechanical cooling
(Y1–OUT terminal)
COOL Y2—IN OFF ON/OFF
SECOND STAGE COOLING DEMAND (Y2–IN)
Y2–I signal from space thermostat our unitary controller for second
stage cooling.
ON = 24 vac on terminal Y2–I
OFF = 0 vac on terminal Y2–I
COOL Y2—OUT OFF ON/OFF
SECOND STAGE COOLING RELAY OUTPUT
Cool Stage 2 Relay Output to mechanical cooling
(Y2–OUT terminal).
MA TEMP
e
_ _ . _ F
0°F to 140°F
(–17°C to 60°C)
SUPPLY AIR TEMPERATURE, Cooling Mode
Displays value of measured mixed air from MAT sensor.
Displays _ _ . _ F if not connected, short or out-of-range.
DA TEMP _ _ . _ F
0°F to 140°F
(–17°C to 60°C)
DISCHARGE AIR TEMPERATURE, after Heating section
Displays when Discharge Air sensor is connected and displays
measured discharge temperature.
Displays _ _ . _F if sensor sends invalid value, if not connected, short
or out-of-range.
OA TEMP _ _ . _ F
–40°F to 140°F
(–40°C to 60°C)
OUTSIDE AIR TEMP
Displays measured value of outdoor air temperature.
Displays _ _ . _F if sensor sends invalid value, short or out-of-range.
OA HUM _ _ % 0 to 100%
OUTSIDE AIR RELATIVE HUMIDITY
Displays measured value of outdoor humidity from OA sensor.
Displays _ _% if not connected short, or out-of-range.
RA TEMP _ _ . _ F
0°F to 140°F
(–17°C to 60°C)
RETURN AIR TEMPERATURE
Displays measured value of return air temperature from RAT sensor.
Displays _ _ . _ F if sensor sends invalid value, if not connected,
short or out-of-range
RA HUM _ _ % 0 to 100%
RETURN AIR RELATIVE HUMIDITY
Displays measured value of return air humidity from RA sensor.
Displays _ _% if sensor sends invalid value, if not connected, short
or out-of-range.
IN CO2 _ _ _ ppm 0 to 2000 ppm
SPACE/RETURN AIR CO
2
Displays value of measured CO
2
from CO
2
sensor. Invalid if not
connected, short or out-of-range.