APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table D — Mode — Pressures
ITEM EXPANSION RANGE UNITS
CCN TABLE/
SUB-TABLE
CCN POINT
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
PRESSURES STATUS DISPLAY
SSP.A Suction Pressure A xxx.x psig UINPUT SSP_A
SCP.A Condenser Pressure A xxx.x psig SCP_A
SSP.B Suction Pressure B xxx.x psig SSP_B
SCP.B Condenser Pressure B xxx.x psig SCP_B
Table E — Mode — Inputs
ITEM EXPANSION RANGE UNITS
CCN TABLE/Sub-
TABLE
CCN POINT
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
INPUTS STATUS DISPLAY
STAT Thermostat Inputs UINPUT
Y1 Thermostat Y1 Input Off/On Y1 forcible forcible
Y2 Thermostat Y2 Input Off/On Y2 forcible forcible
W1 Thermostat W1 Input Off/On W1 forcible forcible
W2 Thermostat W2 Input Off/On W2 forcible forcible
G Thermostat G Input Off/On G forcible forcible
GEN.I General Inputs
FIL.S Filter Status Switch Clean/Dirty FILTSTAT forcible
FAN.S Fan Status Switch Off/On FAN_STAT forcible
FDWN Fire Shutdown Switch Off/On FIREDOWN forcible
ENTH Outdoor Enthalpy Switch Low/High ENTHALPY forcible forcible
RM.OC Remote Occupancy Switch Off/On REM_OCC forcible forcible
HUM Space Humidity Switch Low/High HUM_STAT forcible forcible
IGC.F IGC Fan Request Off/On IDF_FDBK
CS.A1 Compressor A1 Feedback Off/On CS_A1
CS.B1 Compressor B1 Feedback Off/On CS_B1
AIR.Q Air Quality Inputs
IAQ.S IAQ Level (switch) Low/High IAQIN forcible forcible
IAQ IAQ Level (sensor) xxxx IAQ forcible forcible
OAQ OAQ Level (sensor) xxxx OAQ forcible forcible
SP.RH Space Humidity Sensor xxx.x % SPRH forcible forcible
Table F — Mode — Outputs
ITEM EXPANSION RANGE UNITS
CCN TABLE/
SUB-TABLE
CCN POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
OUTPUTS STATUS DISPLAY
FANS Fan Outputs UOUTPUT
F.SPD Commanded Fan Speed xxx % FANSPEED
IDF.1 Indoor Fan Speed Relay 1 Off/On IDF_1
IDF.2 Indoor Fan Speed Relay 2 Off/On IDF_2
IDF.3 Indoor Fan Speed Relay 3 Off/On IDF_3
COOL Cool Outputs
CMP.A Circuit A Compressor Off/On COMP_A
CMP.B Circuit B Compressor Off/On COMP_B
CRC Cool->Reheat1 Control Off/On CRC
RH2.A Reheat2 Valve A Off/On RH2_A
RH2.B Reheat2 Valve B Off/On RH2_B
HEAT Heat Outputs
HT.1 Heat Stage 1 Relay Off/On HEAT_1
HT.2 Heat Stage 2 Relay Off/On HEAT_2
ECON Economizer Outputs
EC.CP Econo Commanded Position 0 to 100 % ECONOCMD forcible forcible
EC.AP Econo Actual Position 0 to 100 % ECONOPOS
PE.1 Power Exhaust 1 Relay Off/On PE_1 forcible
PE.2 Power Exhaust 2 Relay Off/On PE_2 forcible
ALRM Alarm Relay Off/On ALMOUT forcible