APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table G — Mode — Set Points
ITEM EXPANSION RANGE UNITS DEFAULT CCN TABLE/SUB-TABLE CCN POINT
SETPOINT CONFIGURATION
SETPOINTS SET_PNT
OCSP Occupied Cool Setpoint 55 to 80 °F 78 OCSP
UCSP Unoccupied Cool Setpoint 65 to 95 °F 85 UCSP
OHSP Occupied Heat Setpoint 55 to 80 °F 68 OHSP
UHSP Unoccupied Heat Setpoint 40 to 80 °F 60 UHSP
GAP Heat-Cool Setpoint Gap 2 to 10 ^F 5 HCSP_GAP
STO.R SPT Offset Range (+/- ) 0 to 5 ^F 5 SPTO_RNG
RH.SP Space RH Occupied SP 30 to 100 % 50 SPRH_SP
RH.UN Space RH Unoccupied SP 30 to 100 % 80 SPRH_USP
RH.DB Space RH Deadband 2 to 20 % 8 SPRH_DB
RH.HB Reheat Heat SP Deadband - 5 to 5 ^F 2 RH_HSPDB
Table H — Mode — Configuration
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT
PAGE
NO.
CONFIGURATION
SERVICE
CONFIG.
DISP DISPLAY CONFIGURATION DISPLAY
METR Metric Display No/Yes No DISPUNIT 16
LANG Language Selection
0=English
1=Spanish
2=French
3=Portuguese
LANGUAGE 16
PROT Password Enable Disable/Enable Enable PASS_EBL 16
PSWD Service Password 0000 to 9999 1111 PASSWORD 16
TEST Test Display LEDs Off/On Off
(display only, not
in table)
DISPTEST 16
UNIT UNIT CONFIGURATION UNIT
S.DLY Startup Delay 10 to 600 sec 30 STARTDLY 16
U.CTL Unit Control Type
2=Thermostat
3=Space Sensor
2 CTL_TYPE 16
T.CTL Thermostat Control Type
0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0 STATTYPE 16
FN.SW Fan Status Switch
0=No Switch
1=Normal Open
2=Normal Closed
0 FANSTCFG 17
FL.SW Filter Status Switch
0=No Switch
1=Normal Open
2=Normal Closed
0 FILSTCFG 17
FS.SW Fire Shutdown Switch
0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
SHTDNCFG 17
RM.SW Remote Occupancy Switch
0=No Switch
1=Normal Open
2=Normal Closed
0 REMOCCFG 17
SAT.T SAT Settling Time 10 to 900 sec 240 SAT_SET 17
RAT.S RAT Sensor Installed No/Yes No RAT_SENS 17
RH.S RH Sensor on OAQ Input No/Yes No RH_OAQ 17
RH.SW Space Humidity Switch
0=No Switch
1=Normal Open
2=Normal Closed
0 HUMSTCFG 17
TCS.C Temp Cmp Strt Cool Factr 0 to 60 mins 0 TCSTCOOL 17
TCS.H Temp Cmp Strt Heat Factr 0 to 60 mins 0 TCSTHEAT 17
I.FAN INDOOR FAN CONFIG AFAN_CFG
FTYP Indoor Fan Type
0=1- SPEED
1=LEN VFD
0
1: SAV option
FAN_TYPE 19
NSPD Number of Speeds 2, 3, or 7 2 NUM_SPDS 19
OC.FN Fan On When Occupied No/Yes Yes OCC_FAN 19
IDF.F Shut Down on IDF Failure No/Yes Yes FATALFAN 16
FS.MX Supply Fan Maximum Speed 80 to 100 100 SPEEDMAX 19
FS.VN Fan Speed - Ventilation 0 to 100 % 67 FSPDVENT 19
FS.AQ
Fan Speed - IAQ Override 0 to 100 % 100 FSPDAQOR 20