108
 APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table G — Mode — Set Points
ITEM  EXPANSION  RANGE  UNITS  DEFAULT CCN TABLE/SUB-TABLE  CCN POINT 
SETPOINT CONFIGURATION
SETPOINTS  SET_PNT
OCSP  Occupied Cool Setpoint  55 to 80  °F  78  OCSP
UCSP Unoccupied Cool Setpoint  65 to 95  °F  85  UCSP
OHSP  Occupied Heat Setpoint  55 to 80  °F  68  OHSP
UHSP  Unoccupied Heat Setpoint  40 to 80  °F  60  UHSP
GAP  Heat-Cool Setpoint Gap  2 to 10  ^F  5  HCSP_GAP
STO.R  SPT Offset Range (+/- )  0 to 5  ^F  5  SPTO_RNG
RH.SP  Space RH Occupied SP  30 to 100  %  50  SPRH_SP
RH.UN  Space RH Unoccupied SP  30 to 100  %  80  SPRH_USP
RH.DB  Space RH Deadband  2 to 20  %  8  SPRH_DB
RH.HB  Reheat Heat SP Deadband  - 5 to 5  ^F  2  RH_HSPDB
Table H — Mode — Configuration
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE 
CCN POINT 
PAGE
NO.
CONFIGURATION 
SERVICE
CONFIG.
DISP  DISPLAY CONFIGURATION DISPLAY
METR  Metric Display  No/Yes  No  DISPUNIT  16
LANG  Language Selection 
0=English
1=Spanish
2=French
3=Portuguese
LANGUAGE 16
PROT  Password Enable  Disable/Enable  Enable  PASS_EBL  16
PSWD  Service Password  0000 to 9999  1111  PASSWORD  16
TEST  Test Display LEDs  Off/On  Off 
(display only, not 
in table)
DISPTEST 16
UNIT  UNIT CONFIGURATION  UNIT
S.DLY  Startup Delay  10 to 600  sec  30  STARTDLY  16
U.CTL  Unit Control Type 
2=Thermostat
3=Space Sensor
2 CTL_TYPE 16
T.CTL  Thermostat Control Type 
0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0 STATTYPE 16
FN.SW  Fan Status Switch 
0=No Switch
1=Normal Open
2=Normal Closed
0 FANSTCFG 17
FL.SW  Filter Status Switch 
0=No Switch
1=Normal Open
2=Normal Closed
0 FILSTCFG 17
FS.SW  Fire Shutdown Switch 
0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
SHTDNCFG 17
RM.SW  Remote Occupancy Switch 
0=No Switch
1=Normal Open
2=Normal Closed
0 REMOCCFG 17
SAT.T  SAT Settling Time  10 to 900  sec  240  SAT_SET  17
RAT.S  RAT Sensor Installed  No/Yes  No  RAT_SENS  17
RH.S  RH Sensor on OAQ Input  No/Yes  No  RH_OAQ  17
RH.SW  Space Humidity Switch 
0=No Switch
1=Normal Open
2=Normal Closed
0 HUMSTCFG 17
TCS.C  Temp Cmp Strt Cool Factr  0 to 60  mins  0  TCSTCOOL  17
TCS.H  Temp Cmp Strt Heat Factr  0 to 60 mins  0  TCSTHEAT  17
I.FAN  INDOOR FAN CONFIG  AFAN_CFG
FTYP  Indoor Fan Type 
0=1- SPEED
1=LEN VFD
0
1: SAV option
FAN_TYPE 19
NSPD  Number of Speeds  2, 3, or 7 2 NUM_SPDS  19
OC.FN  Fan On When Occupied  No/Yes  Yes  OCC_FAN  19
IDF.F  Shut Down on IDF Failure  No/Yes  Yes  FATALFAN  16
FS.MX  Supply Fan Maximum Speed  80 to 100  100  SPEEDMAX  19
FS.VN  Fan Speed - Ventilation  0 to 100  % 67  FSPDVENT 19
FS.AQ 
Fan Speed - IAQ Override  0 to 100  %  100  FSPDAQOR  20