 APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table K — Mode — Operating Modes (cont)
ITEM EXPANSION RANGE UNITS 
CCN TABLE/Sub-
TABLE
CCN POINT
CCN WRITE 
STATUS
DISPLAY 
WRITE 
STATUS
OK.HT  OK to Select Heat Mode?  No/Yes  OKTOHEAT
MS.TG  Mode Select Timeguard  xxx  secs  HEATMSTG
H.LOC  Heat OAT Lockout  No/Yes  HEATLOCK
HT.LO  Heating Lockout Temp  xxx  °F  OATLHEAT
IGC.F  IGC Fan Request  IDF_FDBK
F.MOD Indoor Fan Mode  x  IDF_MODE
F.SPD  Commanded Fan Speed  xxx  %  FANSPEED
AVL.H  Available Heating Stages  x  AVLHSTGS
REQ.H  Requested Heating Stages  x  REQHSTGS
LMT.H  Max Heat Stage In Effect  x  HSTGLIMT
ACT.H  Actual Heating Stages  x  ACTHSTGS
HT.1  Heat Stage 1 Relay  Off/On  HEAT_1
HT.2  Heat Stage 2 Relay  Off/On  HEAT_2
SAT  Supply Air Temperature
SAT.H  SAT Heat Mode Sensing  Disable/Enable  SAT_HEAT
SAT  Supply Air Temperature  xxx.x  °F  SAT_DISP
SAM.L  Maximum SAT Lower Level  xxx.x  °F  SATMAX_L
SAM.U  Maximum SAT Upper Level  xxx.x  °F  SATMAX_H
SPT  Space Temperature
SPT  Space Temperature  xxx.x  °F  SPACE_T  forcible  forcible
DMD.H  Heating Demand  xxx.x  ^F  HEAT_DMD
TRD.H  Heat Demand d/dt (F/min)  xxx.x  HTDTREND
HT.PD  SPT Heat Demand (+) Level  xx.x  ^F  HDEM_POS
HT.ND  SPT Heat Demand (- ) Level  xx.x  ^F  HDEM_NEG
H.LAG  Heat Thermal Lag Factor  x.x  HEAT_LAG
ECON  Economizer Diagnostic  ECONDIAG
EC.EN  Economizer Installed  No/Yes  ECONO
OK.EC  OK to Use Economizer?  No/Yes  ECONCOOL
OCC  Currently Occupied  No/Yes  OCCUPIED  forcible  forcible
F.MOD  Indoor Fan Mode  x  IDF_MODE
F.SPD  Commanded Fan Speed  xxx  %  FANSPEED
COOL  In Cooling Mode?  No/Yes  IN_COOL
OAT  Outdoor Air Temperature  xxx.x  °F  OA_TEMP  forcible  forcible
RAT  Return Air Temperature  xxx.x  °F  RETURN_T  forcible
E.LOC  Econo Cool OAT Lockout  No/Yes  ECONLOCK
D.LOC  Econo Diff Dbulb Lockout  No/Yes  DFDBLOCK
EH.LO  Econo Cool Hi Temp Limit  xxx  °F  OATLECLH
EL.LO  Econo Cool Lo Temp Limit  xxx °F  OATLECLL
FC.LO  Free Cool Low Temp Limit  xxx  °F  OATLUEFC
EN.LO  Econo Cool Enth Lockout  No/Yes  ENTHLOCK
EC.MX  Econo Cool Max Position  xxx  %  ECONOMAX
AQ.DV  IAQ DCV Mode  No/Yes  IN_IAQDV
AQ.MN  Econo Min IAQ Position  xxx  %  IAQMINP
AQ.OV  IAQ Override Mode  No/Yes  IN_IAQOV
OVR.P  IAQ Override Position xxx  %  IAQOVPOS
AQ.LO 
OAQ Lockout Mode  No/Yes  IN_OAQLO
OAQ.L  OAQ Lockout Limit  xxxx  OAQLOCK
LP.OV  Lo Refrig Press Override  No/Yes  IN_LPOV
EC.CP  Econo Commanded Position  xxx  %  ECONOCMD  forcible  forcible
EC.AP  Econo Actual Position  xxx  %  ECONOPOS
EC.MP  Min Position in Effect  xxx  %  MIN_POS  forcible  forcible
C.ANG  Actuator Control Angle  xx.x  CTLANGLE
E.CAL  Economizer Calibrating  No/Yes  ECOINCAL