118
 APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table K — Mode — Operating Modes (cont)
ITEM EXPANSION RANGE UNITS 
CCN TABLE/Sub-
TABLE
CCN POINT
CCN WRITE 
STATUS
DISPLAY 
WRITE 
STATUS
OAU  Outside Air Unit Diagnostic  OAU_DIAG
OA.RN  OAU System Run State 
1=AUTO
2=OFF
3=TEST
OAU_RUN
OA.OP  OAU Operating Mode 
0=Off
1=ERV (DCV)
2=Free Cooling
3=OA Tempering
4=Defrost
5=Test
6=Ext. Mode 1
7=Ext. Mode 2
8=Ext. Mode 3
OAU_MODE
2P.DM  OAU 2- position Damper  Close/Open  OAUDMPR
WHL OAU Wheel Speed  xxx  %  OAUWHEEL
LAT  OAU Leaving Air Temp  xxx.x  °F  OAU_LAT
EXAT  OAU Exhaust Air Temp  xxx.x  °F  OAU_EXAT
OA.MN  Minimum Outside Air CFM  xxxxx  CFM  MINOACFM
DCV.M  Min DCV Outside Air CFM  xxxxx  CFM  MINDCVSP
OA.FS  OAU OA Fan Speed  xxx  %  OAFANSPD
A.OA  Actual Outside Air CFM  xxxxx  CFM  ACTOACFM
C.OA  Command Outside Air CFM  xxxxx  CFM  CMDOACFM
PE.OF  Power Exhaust CFM Offset  xxxxx  CFM  EXOFFSET
EX.FS  OAU Exhaust Fan Speed  xxx  %  OAUPESPD
A.EX  Actual Exhaust Air CFM xxxxx  CFM  ACTEXCFM
C.EX  Command Exhaust Air CFM  xxxxx  CFM  CMDEXCFM
BP.SP  Building Pressure Setpnt  x.xx  in H2O  OAU_BPSP
BP  Building Pressure  x.xx  in H2O  OAU_BP
TM.LO  OA Tempring Lockout Temp  xx  °F  OATMPLOC
TM.SP  OA Tempring SAT Setpoint  xx  °F  OATMPSPT
OA.HT  OAU Tempering Heater  xxx  %  OAHEATER
ALM.1  OAU Motor Failure Alarm  Off/On  OAUALRM1
ALM.2  OAU Dirty Filter Alarm  Off/On  OAUALRM2
ALM.3  OA Low CFM Alarm  Off/On  OAUALRM3
ALM.4  OAU Alarm  Off/On  OAUALRM4
DMD.L  DEMAND LIMITING  DMDL
D.LMT  Demand Limit In Effect  No/Yes  MODEDMDL
LMT.C  Max Cool Stage In Effect  x  CSTGLIMT
LMT.H  Max Heat Stage In Effect  x  HSTGLIMT
REDL  Redline Activated  No/Yes  MODEREDL
SHED  Loadshed Activated  No/Yes  MODESHED
MAX.C  Max Allowed Cool Stages  x  MAXCSTGS
MAX.H  Max Allowed Heat Stages  x  MAXHSTGS
(Display TRIM 
- see 
Configuration)
Sensor Calibration  TRIM
Space Temp Calibration  -30 to 130  °F  SPT_CAL  forcible
Space Temp Trim  -30 to 30  ^F  SPT_OFF  forcible
Supply Air Temp Calib.  -30 to 130  °F  SAT_CAL  forcible
Supply Air Temp Trim  -30 to 30  ^F  SAT_OFF  forcible
Return Air Temp Calib.  -30 to 130  °F  RAT_CAL  forcible
Return Air Temp Trim  -30 to 30  ^F  RAT_OFF  forcible