131
HMZR Humidimizer Config HMZR_CFG
REHT Humidimizer Equipped No/Yes
No
Yes: Humidi-
MiZer FIOP
REHEAT
R.DEC Reheat2 Stage Decr. Time 0 to 999 secs 60 RSTAGDEC
R.INC Reheat2 Stage Incr. Time 0 to 999 secs 300 RSTAGINC
RA.LO Reheat2 OAT Limit A 20 to 70 °F 40 OATLRH_A
RA.LP Reheat2 SSP Lo Limit A 50 to 100 psig 80 RHSSPL_A
RA.HP Reheat2 SSP Hi Limit A 50 to 100 psig 90 RHSSPH_A
RB.LO Reheat2 OAT Limit B 20 to 70 °F 50 OATLRH_B
RB.LP Reheat2 SSP Lo Limit B 50 to 100 psig 80 RHSSPL_B
RB.HP Reheat2 SSP Hi Limit B 50 to 100 psig 90 RHSSPH_B
HEAT Heating Configuration HEAT_CFG
HT.TY Type of Heat Installed
0=No Heat
1=Gas2=Electric
0 (50 series with
no electric heat)
1 (48 series)
2 (50 series with
electric heat)
HEATTYPE
N.HTR Number of Heat Stages 1 to 2
2 (all except
below)
1 (48 series Low
Nox or Single
Phase Unit)
1 (50 series 04-
14 with low heat)
1 (50 series 04-
12 with medium
heat)
1 (50 series 04,
05, with high
heat)
1 (50 series 575v
07- 09, with high
heat)
1 (50 series 460v
07, with high
heat)
NUM_HEAT
MRT.H Heat Minimum On Time 60 to 999 sec 120 HMIN_ON
MOT.H Heat Minimum Off Time 60 to 999 sec 120 HMIN_OFF
H.DEC Heat Stage Decrease Time 120 to 999 sec 300 HSTAGDEC
H.INC Heat Stage Increase Time 120 to 999 sec 450 HSTAGINC
FOD.E Fan-off Delay, Elect Heat 10 to 600 sec 30 ELEC_FOD
FOD.G Fan-off Delay, Gas Heat 45 to 600 sec 45 GAS_FOD
HT.LO Heating Lockout Temp 40 to 125 °F 75 OATLHEAT
SAT
SAT.H SAT Heat Mode Sensing Disable/Enable Disable SAT_HEAT
SAM.L Maximum SAT Lower Level 85 to 200 °F 140 SATMAX_L
SAM.U Maximum SAT Upper Level 85 to 200 °F 160 SATMAX_H
SPT Space Temperature
HT.PD SPT Heat Demand (+) Level 0.5 to 5 ^F 1 HDEM_POS
HT.ND SPT Heat Demand (-) Level - 5 to - 0.5 ^F -1 HDEM_NEG
H.LAG Heat Thermal Lag Factor 0 to 5 1 HEAT_LAG
ECON Economizer Configuration ECON_CFG
EC.EN Economizer Installed No/Yes
No: no FIOP
Yes: FIOP
ECONO
E.CTL Economizer Control Type
1=Dig/Position
2=Dig/Command
3=Analog Ctrl
1 ECON_CTL
MP.25 Econ Min at 25% Fanspeed 0 to 100 % 0 MINP_25
MP.50 Econ Min at 50% Fanspeed 0 to 100 % 0 MINP_50
MP.75 Econ Min at 75% Fanspeed 0 to 100 % 0 MINP_75
MP.MX
Econ Min at Max Fanspeed 0 to 100 %
30
0: FIOP EnergyX
MINP_MAX
EC.MX Econo Cool Max Position 0 to 100 % 100 ECONOMAX
M.ANG Min Actuator Ctrl Angle 75 to 90 88 MINANGLE
EH.LO Econo Cool Hi Temp Limit 40 to 100 °F 65 OATLECLH
EL.LO Econo Cool Lo Temp Limit -30 to 50 °F 0 OATLECLL
APPENDIX C — VARIABLE FREQUENCY DRIVE (VFD) (cont)
Table X — Mode — Configuration (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
Sub- TABLE
CCN POINT ENTRY