132
ECON Economizer Configuration ECON_CFG
DF.DB Diff Dry Bulb Control
0=Disable
1=RAT - 0°F
2=RAT - 2°F
3=RAT - 4°F
4=RAT - 6°F
0=Disable DIFFBULB
UEFC Unoccupied Free Cooling
0=Disabled
1=Unoccpied
2=PreOccupancy
2 UEFC_CFG
FC.TM Free Cool PreOcc Time 1 to 9999 mins 120 UEFCTIME
FC.LO Free Cool Low Temp Limit -30 to 70 °F 50 OATLUEFC
PE.EN Power Exhaust Installed No/Yes
No: no FIOP
Yes: FIOP
PE_ENABL
PE.1 PE Stage1 Econo Position 0 to 100 % 40 PE1_POS
PE.2 PE Stage2 Econo Position 0 to 100 % 75 PE2_POS
PE1C Power Exhaust Stage1 CFM 0 to 15000 CFM
800 (04- 07)
1600 (08- 14)
3200 (17- 28)
PE1_CFM
PE2C Power Exhaust Stage2 CFM 0 to 15000 CFM 0 PE2_CFM
IDF.C Indoor Fan Max Speed CFM 500 to 15000 CFM
2000 (04- 07)
4000 (08-14)
8000 (17-28)
IDF_CFM
EN.SW Enthalpy Switch
0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
ENTHLCFG
E.TRV Economizer Travel Time 5 to 300 secs 150 ECONOTRV
E.MXB Bottom Stage Max Econo 0 to 100 % 50 ECONMAXB
E.MXT Top Stage Max Econo 0 to 100 %
25 (03-14)
0 (17- 28)
ECONMAXT
LOG.F Log Title 24 Faults No/Yes T24LOGFL
EC.MD T24 Econ Move Detect 1 to 10 T24ECMDB
EC.ST T24 Econ Move SAT Test 10 to 20 T 24ECSTS
S.CHG T24 Econ Move SAT Change 0 to 5 T24SATMD
E.SOD T24 Econ RAT-OAT Diff 5 to 20 T24RATDF
E.CHD T24 Heat/Cool End Delay 0 to 60 T24CHDLY
ET.MN T24 Test Minimum Pos. 0 to 50 T24TSTMN
ET.MX T24 Test Maximum Pos. 50 to 100 T24TSTMX
AIR.Q Air Quality Config. IAQ_CFG
IA.CF IAQ Analog Input Config
0=No IAQ
1=DCV
2=Override IAQ
3=Ctrl Min Pos
0: no FIOP
1: FIOP
IAQANCFG
IA.FN IAQ Analog Fan Config
0=Never
1=Occupied
2=Always
0 IAQANFAN
II.CF IAQ Switch Input Config
0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0IAQINCFG
II.FN IAQ Switch Fan Config
0=Never
1=Occupied
2=Always
0 IAQINFAN
AQ.MN Econo Min IAQ Position 0 to 100 %
10
0: FIOP EnergyX
IAQMINP
OVR.P IAQ Override Position 0 to 100 % 100 IAQOVPOS
OA.CF OAQ Analog Input Config
0=No OAQ
1=DCV
2=Lockout OAQ
0 OAQANCFG
OAQ.L OAQ Lockout Limit 0 to 5000 600 OAQLOCK
AQD.L AQ Differential Low 0 to 5000 100 DAQ_LOW
AQD.H AQ Differential High 0 to 5000 700 DAQ_HIGH
DF.ON Fan On AQ Differential 0 to 5000 600 DAQFNON
DF.OF Fan Off AQ Differential 0 to 5000 200 DAQFNOFF
I.4M IAQ Sensor Value at 4mA 0 to 5000 0 IAQ_4MA
I.20M IAQ Sensor Value at 20mA 0 to 5000 2000 IAQ_20MA
O.4M OAQ Sensor Value at 4mA 0 to 5000 0 OAQ_4MA
O.20M OAQ Sensor Value at 20mA 0 to 5000 2000 OAQ_20MA
APPENDIX C — VARIABLE FREQUENCY DRIVE (VFD) (cont)
Table X — Mode — Configuration (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
Sub- TABLE
CCN POINT ENTRY