EasyManuals Logo

Carrier 48HC D17 Series User Manual

Carrier 48HC D17 Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
36
OPERATIONAL TEST NOTICE
Failure to follow this NOTICE can result in an
unnecessary evacuation of the facility.
If the smoke detector is connected to a fire alarm
system, first notify the proper authorities that the
detector is undergoing maintenance then disable the
relevant circuit to avoid generating a false alarm.
NOTICE
1. Disconnect power from the duct detector then remove
the sensor’s cover. See Fig. 44.
Airow
HVAC duct
Sampling
tube
Retainer
clip
Optic
plate
Optic
housing
Sensor
housing
C07305
Fig. 44 -- Sensor Cleaning Diagram
2. Using a vacuum cleaner, clean compressed air, or a
soft bristle brush, remove loose dirt and debris from
inside the sensor housing and cover.
Use isopropyl alcohol and a lint--free cloth to remove
dirt and other contaminants from the gasket on the
sensors cover.
3. Squeeze the retainer clips on both sides of the optic
housing then lift the housing away from the printed
circuit board.
4. Gently remove dirt and debris from around the optic
plate and inside the optic housing.
5. Replace the optic housing and sensor cover.
6. Connect power to the duct detector then perform a
sensor alarm test.
INDICATORS
Normal State
The smoke detector operates in the normal state in the
absence of any trouble conditions and when its sensing
chamber is free of smoke. In the normal state, the Power
LED on both the sensor and the controller are on and all
other LEDs are off.
Alarm State
The smoke detector enters the alarm state when the
amount of smoke particulate in the sensors sensing
chamber exceeds the alarm threshold value. See Table 5.
Upon entering the alarm state:
S The sensors Alarm LED and the controllers Alarm LED
turn on.
S The contacts on the controllers two auxiliary relays
switch positions.
S The contacts on the controllers alarm initiation relay
close.
S The controllers remote alarm LED output is activated
(turned on).
S The controllers high impedance multiple fan shutdown
control line is pulled to ground Trouble state.
The SuperDuct duct smoke detector enters the trouble
state under the following conditions:
S A sensors cover is removed and 20 minutes pass before
it is properly secured.
S A sensors environmental compensation limit is reached
(100% dirty).
S A wiring fault between a sensor and the controller is
detected.
An internal sensor fault is detected upon entering the
trouble state:
S The contacts on the controllers supervisory relay switch
positions. (See Fig. 45.)
S If a sensor trouble, the sensors Trouble LED the
controllers Trouble LED turn on.
S If 100% dirty, the sensors Dirty LED turns on and the
controllers Trouble LED flashes continuously.
S If a wiring fault between a sensor and the controller, the
controllers Trouble LED turns on but not the sensors.
Alarm
Power
Test/reset
switch
Trouble
C07298
Fig. 45 -- Controller Assembly
NOTE: All troubles are latched by the duct smoke
detector. The trouble condition must be cleared and then
the duct smoke detector must be reset in order to restore it
to the normal state.
48HC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 48HC D17 Series and is the answer not in the manual?

Carrier 48HC D17 Series Specifications

General IconGeneral
BrandCarrier
Model48HC D17 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals