EasyManua.ls Logo

Carrier 50CO Series - Page 14

Carrier 50CO Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 - TECHNICAL SPECIFICATIONS
Units W 40 W 53 W 78 W 100 W 115
Air ow (m
3
/h) 13 300 13 300 20 500 27 000 27 500
* Maximum operating pressure with G4 ltration / COARSE 65% 175 237 400 124 400
* Maximum operating pressure with F7 ltration / ePM1: 55% 66 148 400 30 395
Total/sensible cooling capacity (kW) 46 / 46 51/ 51 78 / 78 100 / 100 124 / 124
Water ow rate (m
3
/h) 7,9 8,8 13 17 21
"Pressure drop (mWC) (Coil + valve)" 7,5 7,7 7,5 6,2 10
* Conditions: return air 26 °C 40 % (RH)
Water temperature 10/15 °C* Maximum operating pressure dependent on air ow rate. Take o󰀨 approximately 20 Pa if there is a hot water coil on MAGISTER.
The operation point can be adjusted directly via the controller. Hence all the air ow/operating pressure combinations are possible, with the values in the table above as the 
maximum values.
Units W40 W53 W78 W100 W115
Air ow (m
3
/h) 13 300 13 300 20 500 27 000 27 500
* Maximum operating pressure with G4 ltration / COARSE 65% 174 236 400 123 400
* Maximum operating pressure with F7 ltration / ePM1: 55% 67 145 400 30 384
Total/sensible cooling capacity (kW) 56 / 56 60/ 60 94 / 94 132 / 132 124 /124
Water ow rate (m
3
/h) 9,6 10 16 23 21
"Pressure drop (mWC) (Coil + valve)" 10 10 10 10 10
* Conditions: return air 32 °C 35 % (RH)
Water temperature 12/17 °C* Maximum operating pressure dependent on air ow rate. Take o󰀨 approximately 20 Pa if there is a hot water coil on MAGISTER.
The operation point can be adjusted directly via the controller. Hence all the air ow/operating pressure combinations are possible, with the values in the table above as the 
maximum values.
Maximum permitted di󰀨erential pressure on cold water valve:
W40 W53 W78 W100 W115
KV 16 16 25 40 25
∆P max. Three-way valve 300 300 300 260 300
∆P max. Two-way valve 1200 1200 1000 260 1000
11.1.4 - Filter
Filters:
EN 779-2012 e󰀩ciency: G4
ISO16890 e󰀩ciency: COARSE 65%
Thickness: 48 mm
E󰀩ciency: 90% gravimetric
Filter area: 2 x the face area
Fire rating: M1
Filters:
EN 779-2012 e󰀩ciency: F7 
ISO16890 e󰀩ciency: ePM1 55%
Thickness: 48 mm
E󰀩ciency: 85% opacimetric
Filter area: 17 x the face area
Fire rating: M1
CHILLED WATER
W40 W53 W78 W100 W115
Dimensions
1192x600 1192x600
1192x600 1192x600 1140x450
1192x360 1192x360
Number
1 1
3 4 6
1 2
Thickness
G4/COARSE: 65 % (mm)
48 48 48 48 48
Thickness
F7/ePM1: 55 % (mm)
48 48 48 48 48
Pressure drops - clean lters:
CHILLED WATER
W40 W53 W78 W100 W115
Flow rate (m³/h) 10 000 13 300 18 800 24 500 27 500
∆P (Pa) G4/COARSE: 65 % 52 57 52 50 69
∆P (Pa) F7/ePM1: 55% (mm) 140 150 140 130 120
14