13 - MAINTENANCE
For lters for sizes W115
- - Unscrew the clamps on the bottom part of the lter (close-up A)
- Release the lter by pulling up the tab on the top part of the lter (close-up B)
Replace the used lters by new lters. Take care to note the direction of air ow indicated on the new lters.
Always make sure that the lter elements are properly positioned before compressing them or switching the unit back on
Detail A
Detail B
13.2 - Cooling coil
Frequency of servicing
As the cooling coil is protected by a lter, its air circuits require very little maintenance
Always cut the power supply to the unit before any cleaning operations.
13.3 - Electric heater
Frequency of servicing
The electric heater requires very little maintenance. However, the following checks are necessary:
Visually inspect the heating elements, wires and connection cables after every 1500 hours of operation.
Check and retighten the connections once or twice a year.
Sizes W40 to W100 Size W115
Side door
Electric heater
B
B To remove the heaters
- Unscrew the screw and remove the washer, and push the pin backwards to release it from its housing. Carry out this procedure
in reverse when retting.
The electric heater is located behind the exchanger (chilled water coil or direct expansion coil).
Open the side door to access it. Clean using an air nozzle.