37
ELECTRIC HEATERS
The 50FC units can be equipped with field-installed accessory 
electric heaters. The heaters are modular in design, with heater 
frames holding open coil resistance wires strung through ceram-
ic insulators and control contactor(s), using a combination of 
24-v control side break/auto-reset or line-break/auto-reset limit 
switches and a pilot-circuit/manual reset limit switch to protect 
the unit against over-temperature situations. All 50FC model 
electric heaters are one module containing either one or two 
banks of electric heat coils. Heaters may be installed on both 
Standard SCCR and High SCCR rated units.
Heater modules are installed in the compartment below the indoor 
(supply) fan outlet. Access is through the indoor blower access 
panel. Heater modules slide into the compartment on tracks along 
the bottom of the heater opening. See Fig. 46-48.
Each kit (CRHEATER454A00 to CRHEATER471A00) con-
tains the heater module, wire ties, and three 1/4-20 nuts. Refer 
to “Electric Heater Accessory, Single Package Rooftop Units, 
Select 17.5 to 27.5 Tons” for unit electrical data and kit usage. 
Not all available heater modules can be used in every unit. Use 
only those heater modules that are UL listed for use in a specif-
ic size unit. Refer to the label on the unit cabinet regarding 
approved heaters.
NOTE: All vertical supply units with electric heat require a field-
supplied 90-degree elbow. The elbow must be installed in the sup-
ply ductwork below the unit discharged connection.
Refer to accessory instructions for the correct single point kit to 
use when single point power entry is desired. The single point kit 
required varies with the specific heater accessory used.
For units equipped with a non fused disconnect switch, the discon-
nect must be adequately sized for the electric heater. If the discon-
nect switch supplied with the equipment is not sized to handle the 
ampacity of the electric heater accessory kit for cooling units or the 
electric heater accessory kit plus the unit ampacity for heat pump 
units, the electric heater kit must be wired to a separate disconnect 
switch sized to handle the electric heater accessory kit ampacity. Re-
fer to the unit’s nameplate or the product data for the unit.
Heater Installation (All Units)
Perform the following procedure to install the accessory elec-
tric heaters:
1. Turn off power to the unit.
2. Remove electric heater section access panel, control box 
access panel, filter access panel, and blower access panel 
from base rooftop unit. (See Fig. 46.)
3. Remove the block-off plate and save screws. Remove post 
adjacent to control box and post located between filter access 
and blower access. (See Fig. 47.)
4. Insert heater assembly through opening where block-off plate 
was previously removed. Let back end of heaters slide along 
support rails beneath fan deck. (See Fig. 48.)
5. Slide heaters until completely installed such that heater con-
trols are completely in the unit. Using screws saved from Step 
3, secure heater assembly. (See Fig. 49.)
6. Route heater power wires through grommeted notches in ver-
tical fan deck support. (See Fig. 48.) Continue routing wires 
under coil and filter support through the bottom notched sec-
tion of the control box. Avoid sheet metal edges and any pro-
truding screws.
7. To be used with Standard SCCR (5ka) Units Only. Refer to 
Fig. 53 for wiring single point kit accessory when required. 
Using three 1/4-20 nuts, connect power wires to the load side 
of terminal block.
If single point power entry is desired, a single point kit must 
be used. See “Electric Heater Accessory, Single Package 
Rooftop Units, Select 17.5 to 27.5 Tons” for details on 
selecting the correct single point kit for the accessory heater 
being installed. Terminal block and fuse holder can be 
mounted using screws provided, locating the combination 
below unit terminal block. (See Fig. 52.) Heaters will be con-
nected to the load side of the terminal block provided with kit. 
Load side of fuses to be connected to terminal block of main 
unit, at factory-installed option non-fused disconnect switch 
and molded case switch for 230v units with the High SCCR 
(Short-Circuit Current Rating) option or fuse holders for 460v 
units with the High SCCR option. 
For dual power entry, purchase terminal block HY11UC313 
for 208-230 volt applications. Six 1/4-20 field supplied lock 
nuts required (P/N AT56AB171). For 400v-50 Hz, 460v and 
575v-60Hz applications purchase terminal block 
HY11UC125. Three 1/4-20 field-supplied screws required 
(P/N AA45AB167). Mount in pre-drilled holes using field-
supplied fasteners. Connect power leads from heaters to field-
supplied terminal block.
8. Connect low voltage control plug from heater to the control 
plug from unit.
9. Re-install posts previously removed. When re-installing 
screws verify that wires do not come into contact with 
screw tips.
10. Re-install blower access, heater access, filter and control box 
access panels.
11. Mark nameplate with a check mark next to heater installed.
460V HIGH SCCR UNIT INSTALLATION 
(65KA SCCR)
1. Remove shroud screws and shroud. Install fuse block 
assembly in location shown in Fig. 50.
2. Route heater wires to fuse holders.
3. Insert wires in top holes of lugs.
4. Tighten screws in lug to clamp down on wires. 
Torque to 7.9 Nm (70 in.-lb).
5. Repeat for all heater wires.
6. Reattach shroud with 2 screws.
230V HIGH SCCR UNIT INSTALLATION 
(60KA SCCR)
1. Install terminal block assembly in location shown in Fig. 51.
2. Remove cover from terminal block assembly.
3. Route heater wires to terminal block assembly.
NOTE: There may be 2 or 4 wires per leg depending on heat-
er configuration.
4. Heater wires will be either 2 wires per leg or 4 wires per leg. 
Component assembly order is important for maintaining 
secure assembly and maximum distancing between compo-
nents on each leg.
For 4 wire/leg assembly: add lock washers (Item 5), turn bot-
tom two wires so barrel of terminal is down as shown in 
Fig. 51. Add nut (Item 4) and tighten to 9-10 Nm (79 in.-lb). 
Add second lock washer (Item 5), the top two wires shall be 
installed with barrels “up.” Add second nut (Item 4) and 
tighten to 9-10 Nm (79-88 in.-lb).
For 2 wire/lug assembly: add lock washers (Item 5), wire ter-
minal barrels may be up or down. Add nut (Item 4) and tight-
en to 9-10 Nm (79-88 in.-lb).
5. Repeat for all heater wires maintain wire color continuity - 
black to black; yellow to yellow; blue to blue.
6. Remove leg cover from line side of control box main fuse 
block. Install line side power wires into bottom holes of fuse 
block lugs. Maintain wire color continuity. Torque set screw 
in lug 42 Nm (375 in.-lb). Reinstall cover.