51
the CO
2
 sensor output will be 6.7 volts. Line up the point on 
the graph with the left side of the chart to determine that the 
range configuration for the CO
2
 sensor should be 1800 ppm. 
The EconoMi$er IV controller will output the 6.7 volts from 
the CO
2
 sensor to the actuator when the CO
2
 concentration in 
the space is at 1100 ppm. The DCV set point may be left at 
2 volts since the CO
2
 sensor voltage will be ignored by the 
EconoMi$er IV controller until it rises above the 3.6 volt set-
ting of the minimum position potentiometer.
Once the fully occupied damper position has been determined, 
set the maximum damper demand controlled ventilation poten-
tiometer to this position. Do not set to the maximum position 
as this can result in over-ventilation to the space and potential 
high humidity levels.
CO
2
 Sensor Configuration
The CO
2
 sensor has preset standard voltage settings that can be 
selected anytime after the sensor is powered up.
Use setting 1 or 2 for Carrier equipment
1. Press Clear and Mode buttons. Hold at least 5 seconds until 
the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
2
 sensor can be changed anytime 
after the sensor is energized. Follow the steps below to change 
the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds 
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu 
and press Enter.
4. Use the Up/Down button to toggle through each of the nine 
variables, starting with Altitude, until the desired setting is 
reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to 
continue to the next variable.
Dehumidification of Fresh Air with DCV (Demand Controlled 
Ventilation) Control
If normal rooftop heating and cooling operation is not adequate 
for the outdoor humidity level, an energy recovery unit and/or 
a dehumidification option should be considered.
ECONOMI$ER IV PREPARATION
This procedure is used to prepare the EconoMi$er IV for trou-
bleshooting. No troubleshooting or testing is done by perform-
ing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm re-
sistor, and a 5.6 kilo-ohm resistor which are not supplied with 
the EconoMi$er IV.
1. Disconnect power at TR and TR1. All LEDs should be off. 
Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor 
across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals SO and +. 
Connect 1.2 kilo-ohm 4074EJM checkout resistor across 
terminals SO and +.
8. Put 620-ohm resistor across terminals SR and +.
9. Set minimum position, DCV set point, and exhaust poten-
tiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW 
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
DIFFERENTIAL ENTHALPY
To check differential enthalpy:
1. Make sure EconoMi$er
®
 IV preparation procedure has 
been performed.
2. Place 620-ohm resistor across SO and +.
3. Place 1.2 kilo-ohm resistor across SR and +. The Free 
Cool LED should be lit.
4. Remove 620-ohm resistor across SO and +. The Free Cool 
LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal after 
completing troubleshooting.
SINGLE ENTHALPY
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been 
performed.
2. Set the enthalpy potentiometer to A (fully CCW). The 
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free 
Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal after 
completing troubleshooting.
DCV (DEMAND CONTROLLED VENTILATION) AND 
POWER EXHAUST
To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has been 
performed.
2. Ensure terminals AQ and AQ1 are open. The LED for 
both DCV and Exhaust should be off. The actuator should 
be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1 (nega-
tive node). The LED for both DCV and Exhaust should turn 
on. The actuator should drive to between 90 and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust 
LED turns off. The LED should turn off when the potenti-
ometer is approximately 90%. The actuator should remain 
in position.
5. Turn the DCV set point potentiometer CW until the DCV 
LED turns off. The DCV LED should turn off when the 
potentiometer is approximately 9-v. The actuator should 
drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the 
Exhaust LED turns on. The exhaust contacts will close 30 
to 120 seconds after the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to normal after 
completing troubleshooting.
IMPORTANT: Be sure to record the positions of all poten-
tiometers before starting troubleshooting.