45
14 - CONECTIONS
17.4. Connection of the Enhanced c.pCOe expansion module to the control board (optional)
The management of the cooling circuit for the recovery of the
extracted air energy (optional) is done with this module.
It can also be used instead of modules with addresses 8 and 9 with
the following optional:
Low outdoor temperature (GREAT COLD).
Remote COOLING / HEATING.
Proportional humidifi er or overpressure control with exhaust
damper.
Active dehumidifi cation with condensation coil.
Second air quality probe (CO
2
) for installation in the environment
or outdoor.
Constant supply pressure control.
Analog inputs
U5: second air quality probe for installation in the environment or
outdoor (4-20mA / 0…5000 ppm) or air quality probe for the
zone 2 (4-20mA)
U6: di erential pressure sensor for constant supply pressure
control
U8: suction temperature probe of the recovery circuit
U9: low pressure transducer of the recovery circuit
U10: high pressure transducer of the recovery circuit
Digital inputs
U1: remote o of the recovery circuit
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
19.2 K
9.6 K
38.4 K
57.6 K
CAREL
Modbus
ON
OFF
Address ProtBaud
Address Ext Baud Prot
Ext
driver
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
19.2 K
9.6 K
38.4 K
57.6 K
CAREL
Modbus
ON
OFF
ProtBaud
ExtAddress
U2: high pressure switch of the recovery circuit
U3: compressor thermal protection of the recovery circuit
U4: remote COOLING / HEATING
Analog output
U7: proportional humidifier or exhaust damper or control of
the proportional 3WV of the condensation coil with actve
dehumidifi cation
Digital outputs
NO1: compressor of the recovery circuit
NO2: cycle reversing valve of the recovery circuit
NO3: compressor with supplementary crankcase heater
NO4: electrical heater for protection of fresh air damper or solenoid
valve SV1 with actve dehumidifi cation
NO5: confi gurable output (humidifi er, HWC pump, alarm signal,...)
or solenoid valve SV2 with actve dehumidifi cation
NO7: signal of alarm of the recovery circuit
Electronic expansion valve
J7: valve of the recovery circuit
Connection to μPC3 board
J9: connection on Fieldbus1
Power supply
J1: 24 Vac
Enhanced c.pCOe module with address 4: