15 - TECHNICAL AND ELECTRICAL CHARACTERISTICS
Close the sensor by turning the cover clockwise ( g.4).
M16x1,5
Ø > 13mm
Ø > 0.51“
19mm
0.75“
90
±0.3
mm
3.54
±0.11
5mm
0.2“
60
±0.3
mm
2.36
±0.11
Ø > 16mm
Ø > 0.63“
6mm
0.24“
15.2. Air quality probe 4.. 20 mA
There are di󰀨 erent options:
Ambient air quality probe (intallation in the environment).
Return air quality probe (duct-mounted).
Probe installed on the master unit of the SHRD shared network.
This probe must be fixed to the
interior wall of the room to be
conditioned, at ca. 1.5 m height in
the room and at least 50 cm from
the next wall.
It should never be mounted:
- On outside walls.
- In niches or behind curtains.
- Above or near heat sources or shelves.
- On walls covering heat sources such as a chimney.
- In the radiation range of heat sources and lighting bodies e.g.
spotlights.
- In areas exposed to direct solar radiation.
Duct-mounted
This version can be connected to the air duct in these two ways:
Electrical connection
This probe (S10) is con gured as analogue output 4…20 mA (0..2000
ppm), in the analogue input B10 of the control board). Recommended
cable section: 1,5 mm
2.
Cleaning and maintenance
When cleaning the instrument do not use ethyl alcohol, hydrocarbons
(petrol), ammonia and derivatives. Use neutral detergents and water.
Periodically check the aeration slits on the sensor to make sure that
air can ow freely through, without obstructions due to impurities or
dust in the site of installation.
Outdoor installation
M16x1.5
19mm
0.75“
90
±0.3
mm
3.54
±0.11
46mm
1.81“
5mm
0.2“
+V
GND
RH
T
CO2
GND
1
2
3
4
5
6
110
111
109
B10
S10
Electric
cabinet
+V
GND
GND
CO2
NC
Tpassive
Tpassive
1
2
3
4
5
6
7
110
111
109
B10
S10
Electric
cabinet
Ambient probe
Return probe (duct-mounted)
Note: This probe must
be located outdoors but
under cover.
( g.1)
( g.2)
( g.3) ( g.4)
Installation in the environment