59MN7C: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
45
Table 16 – Air Delivery - CFM (with filter)
060C17--14
Available Cooling
Airflow Settings (CFM)
400 450 488 525 555 600 650 700 740 800 875
*
925
975
1000 1050 1138 1200
†
1225
1300
Available Constant Fan
Airflow Settings (CFM)
‡
400
450 488 525 555 600 650 700 740 800 875 925 975
1000 1050
Airflow reduces by 2% -
3% per 0.1 of ESP
above the noted static
for these airflow
settings
Airflow ESP (in. w.c.)
1200 0.7
1225 0.6
1300 0.4
Max Cooling ESP
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM
1405 1370 1340 1310 1275 1245 1210 1180 1145 1115
060C21--20
Available Cooling
Airflow Settings (CFM)
600 650 700 740 800 875 925 975 1000 1050 1138 1200 1225
*
1300
1400 1480 1600 1625
†
1750
1850 1911 2000
Available Constant Fan
Airflow Settings (CFM)
‡
650
700
740 800 875 925 975 1000 1050 1138 1200 1225 1300
1400 1480
Airflow reduces by 2% -
3% per 0.1 of ESP
above the noted static
for these airflow
settings
Airflow Setting ESP (in. w.c.)
1750 0.9
1850 0.7
1911 0.5
2000 0.3
Max Cooling ESP
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM
2060 2025 1995 1955 1920 1885 1845 1805 1765 1720
080C17--14
Available Cooling
Airflow Settings (CFM)
488 525 555 600 650 700 740 800 875
*
925
975 1000 1050
1138 1200
†
1225
1300 1400 1450
Available Constant Fan
Airflow Settings (CFM)
‡
488
525 555 600 650 700 740 800 875
925 975 1000 1050
1138 1200
Airflow reduces by 2% -
3% per 0.1 of ESP
above the noted static
for these airflow
settings
Airflow Setting ESP (in. w.c.)
Max Cooling ESP
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM
1530 1525 1525 1530 1530 1555 1560 1530 1495 1455
080C21--20
Available Cooling
Airflow Settings (CFM)
650 700 740 800 875 925 975 1000 1050 1138 1200 1225
*
1300
1400 1480 1600 1625
†
1750
1850 1911 2000
Available Constant Fan
Airflow Settings (CFM)
‡
650
700 740 800 875 925 975 1000 1050 1138 1200 1225 1300
1400 1480
Airflow reduces by 2% -
3% per 0.1 of ESP
above the noted static
for these airflow
settings
Airflow ESP (in. w.c.)
1911 0.9
2000 0.8
Max Cooling ESP
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM
2025 2030 2030 2035 2035 2040 2010 1970 1925 1880
100C21--22
Available Cooling
Airflow Settings (CFM)
650 700 740 800 875 925 975 1000 1050 1138 1200 1225 1300
*
1400
1480 1600 1625 1750 1850
†
1911
2000 2110
Available Constant Fan
Airflow Settings (CFM)
‡
650
700 740 800 875 925 975 1000 1050 1138 1200 1225 1300
1400
1480
Airflow reduces by 2% -
3% per 0.1 of ESP
above the noted static
for these airflow
settings
Airflow Setting ESP (in. w.c.)
1911 0.9
2000 0.7
2110 0.5
Max Cooling ESP
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM
2190 2195 2200 2195 2165 2125 2085 2040 1995 1950