EasyManua.ls Logo

Carrier AQUASNAP 30RB series - Standard Maintenance Procedures; 12.1 - Level 1 Maintenance Tasks; 12.2 - Level 2 Maintenance Tasks; 12.3 - Level 3+ Maintenance Tasks

Carrier AQUASNAP 30RB series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59
Check the presence and the condition of the electrical
protection devices.
Check the correct operation of all heaters.
Replace the fuses every 3 years or every 15000 hours
(age-hardening).
Check the water connections.
Purge the water circuit (see chapter ‘Water flow control
procedure’).
Clean the water filter (see chapter ‘Water flow control
procedure’).
Fully clean the condensers with a low-pressure jet and
a bio-degradable cleaner (counter-current cleaning -
see chapter ‘Condenser coil - level 2).
Replace the stuffing box packing of the pump after
10000 hours of operation.
Check the unit operating parameters and compare
them with previous values.
Keep and maintain a maintenance sheet, attached to
each HVAC unit.
All these operations require strict observation of adequate
safety measures: individual protection garments, compliance
with all industry regulations, compliance with applicable
local regulations and using common sense.

The maintenance at this level requires specific skills/approval/
tools and know-how and only the manufacturer, his repre-
sentative or authorised agent are permitted to carry out
these operations. These maintenance operations concern
for example:
A major component replacement (compressor,
evaporator),
Any intervention on the refrigerant circuit (handling
refrigerant),
Changing of parameters set at the factory (application
change),
Removal or dismantling of the HVAC unit,
Any intervention due to a missed established
maintenance operation,
Any intervention covered by the warranty.
Any deviation or non-observation of these maintenance criteria will render
the guarantee conditions for the HVAC unit nul and void, and the manufacturer,
Carrier France, will no longer be held responsible.

   
Connection sleeve - Piping to be welded with Victaulic connection Ease-of-installation 30RB 162-802
Energy Management Module EMM - See controls manual Easy connection by wired connection to a building
management system
30RB 162-802
Scrolling Marquee Interface - Remotely installed user interface (communication
bus)
Remote chiller control up to 300 m 30RB 162-802
Power cable connection side extension - Side extension on the power control to allow a
reduced cable bend radius
Use of thicker power cables 30RB 302-802
Connection sleeve, standard unit - Water inlet/outlet extension for connection with a
Victaulic collar on the water inlet/outlet piping
Facilitates connection 30RB 162-262

Air conditioning equipment must be maintained by profes-
sional technicians, whilst routine checks can be carried out
locally by specialised technicians.
Simple preventive maintenance will allow you to get the
best performance from your HVAC unit:
improved cooling performance
reduced power consumption
prevention of accidental component failure
prevention of major time-consuming and costly work
protection of the environment
There are five maintenance levels for HVAC units, as
defined by the AFNOR X60-010 standard.

Simple procedure can be carried out by the user:
Visual inspection for oil traces (sign of a refrigerant leak),
Air heat exchanger (condenser) cleaning - see chapter
‘Condenser coil - level 1’,
Check for removed protection devices, and badly
closed doors/covers,
Check the unit alarm report when the unit does not work
(see report in the 30RB Pro-Dialog Plus control manual).
Verification of the charge in the liquid line sight glass,
Verify that the temperature difference between the
heat exchanger inlet and outlet is correct.
General visual inspection for any signs of deterioration.

This level requires specific know-how in the electrical,
hydronic and mechanical fields. It is possible that these
skills are available locally: existence of a maintenance
service, industrial site, specialised subcontractor.
In these cases, the following maintenance operations are
recommended.
Carry out all level 1 operations, then:
At least once a year tighten the power circuit electrical
connections (see table with tightening torques opposite).
Check the expansion tank for signs of excessive corro-
sion or gas pressure loss and replace it, if necessary.
Check and retighten all control/command connections,
if required (see table with tightening torques opposite).
Remove the dust and clean the interior of the control
boxes, if required.

Table of Contents

Other manuals for Carrier AQUASNAP 30RB series

Related product manuals