W

Minimum bending radius:
non-insulated pipes 72 mm
insulated pipes 106 mm.

WARNING: Disconnect the power supply before carrying
out any work on the unit.
If the electric heater develops a fault, it must be replaced;
this requires the removal of the fan motor assembly: Fig. 17
(17a = screw).
CAUTION: Do not touch the live metal heater elements
when the electric heater is connected to the power supply.
Electric heater replacement procedure:
Remove the filter.
Remove the fan motor assembly access panel.
Identify and note the fan speeds wired to the auto-
transformer terminal block. Disconnect the power
supply cable.
Remove the fan motor assembly.
NOTE: Be careful not to touch the fan blades during
the removal process to avoid unbalancing the fans.
Disconnect the electric heater power supply cables
and remove them through the cable conduit.
Unscrew the defective heater(s) and replace it (them).
Replacement of the fan motor assembly is by the
reversal of the above procedure.


A G3 rear access
B G3 access from below
- None
RIGHT
A 125 mm ø fresh air spigot only
B 8.3 l/s (30 m
3
/h)
C 16.6-44.4 l/s (21/28/36) 60-160 m
3
/h
(75/100/130)
E Motorised fresh air valve adapter ø
125 mm
J 125 mm ø fresh air spigot only
LEFT
K 8.3 l/s (30 m
3
/h)
L 16.6-44.4 l/s (21/28/36) 60-160 m
3
/h
(75/100/130)
N Motorised fresh air valve adapter ø
125 mm
0 None
A 230 V on/o
- None
A NTC
B HDB
D NTC + IAQ board
E Terminal block with plastic cover
F E + relay
G E + relay + fuse holder
K NTC + fuse holder
L NTC + IAQ board + fuse holder
M HDB + fuse holder
R E + fuse holder
B Modular unit with 2 supply air spigots
C Modular unit with 3 supply air spigots
G Modular unit with 1 supply air spigot at the end (in-line conguration)
H Modular unit with 1 supply air spigot at the side (opposite coil)
J Modular unit with 4 supply air spigots
K Modular unit with 5 supply air spigots
M Return air plenum 1 spigot and modular unit 1 supply air spigot (in-line conguration)
N Return air plenum 1 spigot and modular unit 1 supply air spigot (U-shape conguration)
P Return air plenum 2 spigots and modular unit 2 supply air spigots
Q Return air plenum 3 spigots and modular unit 3 supply air spigots
R Return air plenum 4 spigots and modular unit 4 supply air spigots
S Return air plenum 5 spigots and modular unit 5 supply air spigots
T Compact unit with 1 return air spigot and 1 supply air spigot
U Compact unit with 2 return air spigots and 2 supply air spigots
V Compact unit with 3 return air spigots and 3 supply air spigots
NOTE: Terminal 1 = highest speed, Terminal 6 = lowest speed.
Fan set
Codication (last digit)
or option 600
Red wire
Grey wire
Black wire
Wire marked L
Six wired
speeds
Terminal marking (standard wiring), option 600 not selected
and option 570 = NTC or HDB
- None
A Return air sensor
B Supply air sensor
C Change-over sensor
D A + B
E A + B + C
F A + C
G B + C
A 2 pipes right
B 2 pipes left
C 4 pipes right
D 4 pipes left
E 2 pipes/2 wires, right, low pressure
F 2 pipes/2 wires left, low pressure
G 2 pipes/2 wires, right, high pressure
H 2 pipes/2 wires left, high pressure
0 5
1 0
2 1
2 2
2 3
3 1
3 2
3 3
- None
C 2-way valve
D 4-way valve
J 2-way valve + exible piping
K 4-way valve + exible piping
Product type Size
Modication
code
Coils
Supply and
return air plenum
Valves
Valve motors
Control
Sensors
Filter and access
Fresh air
Motor wiring
Product reference
4 2 E M N N C A A A A A A A A A
Digit
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
{
Variable-speed
LEC motor

Table of Contents

Other manuals for Carrier Atmosphera 42EM series

Related product manuals