24. TEST RUNNING
24.1 NOTES
-
Operate testing running after completion of connecting refrigerant piping lines,
drain line and electrical wiring and refrigerant leak test.
- Operate test running after mounting air filters, and front panel of indoor unit.
24.2 STEPS FOR COOLING TEST RUNNING
a. Move circuit breaker to ON position.
b. Operate the system for cooling operation at high fan speed by using wired control.
c. After system operation becomes stabilized:
- Measure low pressure to check correct refrigerant charge. (See figure & table )
- Measure total Amps consumed by the system.
- Measure System working voltage.
Sizes 12K – 18K – 24K – 30K
Sizes 36K – 42K – 48K – 60K – 72K
1. Low Pressure Measuring.
System Cooling Test Running
SYSTEM MODEL
53KDMT12N-718
53KDMT18N-718
53KDMT24N-718
AMBIENT TEMP ºC
35
46
52
35
46
52
35
46
52
LOW PRESSURE PSI
136
145
150
142
148
151
135
145
150.5
TOTAL AMPS
4.7
5.6
6.1
6.6
7.9
8.6
9.0
10.7
11.6
SYSTEM MODEL
53KDMT30N-718
53KDMT36N-718T
53KDHT42N-518T
AMBIENT TEMP ºC
35
46
52
35
46
52
35
46
52
LOW PRESSURE PSI
140
147
151
134
146
152.5
138
151
158
TOTAL AMPS
14.9
17.1
18.3
13.8
17.2
19.0
5.4
6.6
7.2
SYSTEM MODEL
53KDHT48N-518T
53KDHT60N-518T
53KDHT72N-518T
AMBIENT TEMP ºC
35
46
52
35
46
52
35
46
52
LOW PRESSURE PSI
140
150
155
129.5
140
146
130.5
140
165.9
TOTAL AMPS
7.0
8.3
9.0
8.4
9.9
10.7
10.1
11.7
12.6
NOTE
x Readings for system models 53KDMT 12 – 18 – 24 – 30 – 36 at 230 volt and 27 ºC
return air to indoor unit and high speed of indoor unit motor.
x Readings for system models 53KDHT 42 – 48 – 60 – 72 at 400 volt and 27 ºC
return air to indoor unit and high speed of indoor unit motor.