Configuring the system
   
 
 
 
33CONNECTSTAT43    ©2022 Carrier. 
Installation Guide    All rights reserved. 
  19 
 
Parameter Name/Description 
AIR FILTER REMINDER — The number of hours before a SYSTEM EVENT reminds the 
occupant to change the indoor air filter. 
•  If set to OFF, a SYSTEM EVENT will not occur to remind the homeowner to change 
the indoor air filter.  
•  Decrements to the timer happen each hour of total equipment runtime. 
•  Minutes are not stored in non-volatile memory, so a power reset clears out the 
minutes within each hour of run time. 
•  Once the number of hours is initially set or later changed, the filter timer must be 
reset on the SETTINGS screen.  
3000 HRS 
OFF 
500 HRS to 15000 HRS 
(500 hour increments) 
OCCUPANCY OUTPUT — When set to ON-Y3, ON-O/B, or ON-W2, selected relay output 
equals current Occupancy state. Can be used for ECON Enable. 
NOTE  The OCCUPANCY OUTPUT option is not displayed or available if Y3, O, and W2 
relays are being used; i.e. Humidification/ Heat Pump/ 3-stage cooling/ etc.. 
OFF 
OFF 
ON-Y3 
ON-W2 
ON-O/B 
OCCUPANCY INPUT — This setting changes the current heating and cooling setpoints to 
the option selected for MAX HOLD TIME. This occurs when the short is detected on the 
Remote Space Sensor for the duration of 2 to 5 seconds. 
Occupied 
Occupied 
Unoccupied 
HUM OUTPUT — Select which output to use for humidifier.  
NOTE Only unassigned outputs are available. 
  
DEHUM OUTPUT — Select the unassigned output to use for dehumidifier (Humidi-MiZer™). 
NOTE Only unassigned outputs are available. 
LINE FREQUENCY — Used to increment operational timers within the thermostat to 
ensure timing accuracy. 
DEALER NAME — (Optional) This setting identifies the name of the installing contractor 
and could be carried forward from the sensor if input through the local display.  
DEALER PHONE — (Optional) This setting identifies the phone number of the installing 
contractor and can be carried forward from the sensor if input through the local display. 
MSTP MAX MASTERS — Used to identify max number of masters for token passing on 
the MS/TP network. 
MSTP BAUD RATE — The protocol's baud rate (communication speed) on the MS/TP 
network. The baud rate must be the same for all controllers on the network. 
76800 
9600 
19200 
38400 
76800 
115000