Appendix: BACnet Points List
33CONNECTSTAT43 ©2022 Carrier.
Installation Guide All rights reserved.
44
Point Name
Point Access
Units
BACnet Point Name
BACnet
Object ID
Heat Pump Lockout
GATED_WRITE
DEGREES_FAHRENHEIT
HP_LCKOUT
AV:512
Stage Delay
GATED_WRITE
MINUTES
STG_DELAY
AV:513
Forced Stage Up Delay
GATED_WRITE
MINUTES
FRCD_STG_UP
AV:514
Stage Change Temp
Differential
GATED_WRITE
DELTA_DEGREES_FAHRENHEIT
DIFFERENTIAL
AV:515
Line Frequency
GATED_WRITE
HERTZ
LINE_FREQ
AV:516
Indoor Temperature Offset
GATED_WRITE
DELTA_DEGREES_FAHRENHEIT
ID_TEMP_OFF
AV:517
Indoor Humidity Offset
GATED_WRITE
PERCENT_RELATIVE_HUMIDITY
ID_HUM_OFF
AV:518
SAT Temp Offset
GATED_WRITE
DELTA_DEGREES_FAHRENHEIT
SAT_OFFSET
AV:519
Air Filter Hours
READ_ONLY
HOURS
AIR_FLT_HRS
AV:520
Max Setpoint Error
GATED_WRITE
DELTA_DEGREES_FAHRENHEIT
MAX_SP_ERR
AV:521
Indoor Temp Fault Inhibit
GATED_WRITE
MINUTES
ID_TMP_FLT_INHBT
AV:522
1st Stage Cooling Out Status
READ_ONLY
0=OFF
1=ON
Y1_OUT
BV:200
2nd Stage Cooling Out
Status
READ_ONLY
0=OFF
1=ON
Y2_OUT
BV:201
3rd Stage Cooling Out
Status
READ_ONLY
0=OFF
1=ON
Y3_OUT
BV:202
1st Stage Heating Out
Status
READ_ONLY
0=OFF
1=ON
W1_OUT
BV:203
2nd Stage Heating Out
Status
READ_ONLY
0=OFF
1=ON
W2_OUT
BV:204
Fan Out Status
READ_ONLY
0=OFF
1=ON
G_OUT
BV:205
Reversing Valve Out Status
READ_ONLY
0=OFF
1=ON
OB_OUT
BV:206
Occupancy Out Status
READ_ONLY
0=OFF
1=ON
OCC_OUT
BV:208
Humidifier Out Status
READ_ONLY
0=OFF
1=ON
HUM_OUT
BV:209
Dehumidifier Out Status
READ_ONLY
0=OFF
1=ON
DEHUM_OUT
BV:210
Network General Purpose
Out Y3
READ_WRITE
0=OFF
1=ON
NET_GP_Y3_OUT
BV:211
Network General Purpose
Out W2
READ_WRITE
0=OFF
1=ON
NET_GP_W2_OUT
BV:212
Network General Purpose
Out OB
READ_WRITE
0=OFF
1=ON
NET_GP_OB_OUT
BV:213
Wi-Fi Time Synchronization
READ_WRITE
0=DISABLED
1=ENABLED
WIFI_TIME_SYNC
BV:400
Proximity Sensor Enable
READ_WRITE
0=DISABLED
1=ENABLED
PROXIMITY_EN
BV:401
Auto DST Time Shift
READ_WRITE
0=DISABLED
1=ENABLED
AUTO_DST
BV:402