Appendix: BACnet Points List
33CONNECTSTAT43 ©2022 Carrier.
Installation Guide All rights reserved.
45
Point Name
Point Access
Units
BACnet Point Name
BACnet
Object ID
Wi-Fi Enable
READ_WRITE
0=DISABLED
1=ENABLED
WIFI_ENABLE
BV:403
Setpoint Override
READ_WRITE
0=DISABLED
1=ENABLED
SETPT_OVERRIDE
BV:404
BACnet BMS Occupancy
GATED_WRITE
0=UNOCCUPIED
1=OCCUPIED
BMS_OCC
BV:405
Filter Timer Reset
READ_WRITE
0=INACTIVE
1=ACTIVE
FLTR_TMR_RST
BV:406
Network Space Temp Enable
READ_WRITE
0=DISABLED
1=ENABLED
NET_SP_TEMP_EN
BV:407
Network Space Hum Enable
READ_WRITE
0=DISABLED
1=ENABLED
NET_SP_HUM_EN
BV:408
Occupancy Input Polarity
GATED_WRITE
0=OCCUPIED
1=UNOCCUPIED
OCC_IN_POL
BV:500
Auto Mode Allowed
GATED_WRITE
0=NO
1=YES
ALLOW_AUTO
BV:501
Prog Mode Allowed
GATED_WRITE
0=NO
1=YES
ALLOW_PROG
BV:502
Celsius Display
GATED_WRITE
0=F°
1=C°
CELSIUS_DISP
BV:503
Fan On with W
GATED_WRITE
0=NO
1=YES
FAN_WITH_W
BV:504
Rvs Vlv Energized Ht
GATED_WRITE
0=ENERGIZED FOR COOL
1=ENERGIZED FOR HEAT
RVS_VLV_DIR
BV:505
Humidifier Installed
GATED_WRITE
0=NO
1=YES
HUM_INST
BV:506
BMS Occupancy Enable
GATED_WRITE
0=DISABLED
1=ENABLED
BMS_OCC_EN
BV:507
BACnet Config Write Enable
GATED_WRITE
0=DISABLED
1=ENABLED
CFG_WR_EN
BV:511
ID TEMP SENSOR HIGH
READ_ONLY
0=DISABLED
1=ENABLED
ID_TEMP_SENS_HI
BV:900
ID TEMP SENSOR LOW
READ_ONLY
0=INACTIVE
1=ACTIVE
ID_TEMP_SENS_LO
BV:901
REMOTE SENSOR HIGH
READ_ONLY
0=INACTIVE
1=ACTIVE
REM_TEMP_HI
BV:902
REMOTE SENSOR LOW
READ_ONLY
0=INACTIVE
1=ACTIVE
REM_TEMP_LO
BV:903
HUM TEMP SENSOR HIGH
READ_ONLY
0=INACTIVE
1=ACTIVE
HUM_TEMP_HI
BV:904
HUM TEMP SENSOR LOW
READ_ONLY
0=INACTIVE
1=ACTIVE
HUM_TEMP_LO
BV:905
ID TEMP RANGE HIGH
READ_ONLY
0=INACTIVE
1=ACTIVE
ID_TEMP_RNG_HI
BV:906