49
Table 36 — Alarm and Alert Codes (cont)
ALARM/ALERT
CODE
ALARM OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM GENERATED?
ACTION TAKEN
BY CONTROL
RESET METHOD
PROBABLE
CAUSE
47 Alert Circuit A High
Saturated Suction
Temperature
After first 90 seconds,
SST > 55 F (12.8 C) and 
EXV < 1% for 5 minutes
Circuit A shut down Manual Faulty expansion valve,
liquid level sensor or
transducer.
48 Alert Circuit B High
Saturated Suction
Temperature
After first 90 seconds,
SST > 55 F (12.8 C) and 
EXV < 1% for 5 minutes
Circuit B shut down Manual Faulty expansion valve,
liquid level sensor or
transducer.
49 Alarm Loss of Condenser
Flow
Flow switch not closed 
within 1 minute after 
pump is started or if flow 
switch opens during nor-
mal operation for 
> 10 seconds
Chiller shut down Manual Low condenser water 
flow, failed condenser 
pump
50 Alarm Illegal Configuration x Illegal Configuration has 
been entered. Correction 
needed.
Chiller cannot start. See 
Table 38.
Manual Configuration error.
51 Alarm Initial Configuration
Required
No configuration has 
been entered.
Chiller cannot start Manual Configuration omitted.
52 Alarm Unit is in Emergency
Stop
CCN command received 
to shut unit down.
Chiller shut down CCN/Automatic Network command
53 Alarm Cooler Pump Interlock
Failed at Start-Up
Interlock did not close 
within 1 minute after
transition
Chiller shut down. Pump 
turned off.
Automatic Failure of cooler pump, 
cooler pump interlock, or 
flow switch
54 Alarm Cooler Pump Interlock
Opened Unexpectedly
Interlock opened for at 
least 5 seconds during 
operation
Chiller shut down. Pump 
turned off.
Automatic Failure of cooler pump, 
cooler pump interlock, or 
flow switch
55 Alarm Cooler Pump Interlock
Closed When Pump OFF
Interlock closed when 
pump relay is off
Cooler pump remains off. 
Unit prevented from
starting.
Manual Failure of cooler pump 
relay or interlock, welded
contacts
56 Alert Loss of Communication 
with WSM
No communications have 
been received by PSIO-1 
within 5 minutes of trans-
mission.
WSM forces removed. 
Runs under own
control.
Automatic Failed module, wiring 
error, failed transformer, 
loose connection plug, 
wrong address
57 Alert Circuit A Liquid Level 
Sensor Failure
Sensor reads 245 F
(118 C) or -40 F (-40 C)
with SST > 9 F (-12.8 C)
Runs, but controls EXV 
based on Disch. Super-
heat
Automatic Thermistor circuit open, 
faulty liquid level sensor, 
wiring error
58 Alert Circuit B Liquid Level 
Sensor Failure
Sensor reads 245 F
(118 C) or -40 F (-40 C)
with SST > 9 F (-12.8 C)
Runs, but controls EXV 
based on Disch. Super-
heat
Automatic Thermistor circuit open, 
faulty liquid level sensor, 
wiring error
59 Alarm Compressor A1
Pre-Start Oil Pressure
Oil Pump did not build
sufficient pressure during 
pre-lube cycle.
Circuit cannot start Manual Low oil, oil pump failure, 
oil solenoid failure, oil 
transducer failure, check 
valve failed open, oil shut-
off valve closed
60 Alarm Compressor A2
Pre-Start Oil Pressure
Oil Pump did not build
sufficient pressure during 
pre-lube cycle.
Circuit cannot start Manual Low oil, oil pump failure, 
oil solenoid failure, oil 
transducer failure, check 
valve failed open, oil shut-
off valve closed
61 Alarm Compressor B1
Pre-Start Oil Pressure
Oil Pump did not build
sufficient pressure during 
pre-lube cycle.
Circuit cannot start Manual Low oil, oil pump failure, 
oil solenoid failure, oil 
transducer failure, check 
valve failed open, oil shut-
off valve closed
62 Alarm Compressor A2
Pre-Start Oil Pressure
Oil Pump did not build
sufficient pressure during 
pre-lube cycle.
Circuit cannot start Manual Low oil, oil pump failure, 
oil solenoid failure, oil 
transducer failure, check 
valve failed open, oil shut-
off valve closed
63 Alarm Circuit A&B OFF for 
Alerts. Unit down
Control has shut down 
both circuits due to 
alerts.
None Automatic Check individual alarms
64 Alert Circuit A Loss of Charge Discharge pressure
reading < 10 PSIG for 
30 seconds
Circuit A shut down Manual Refrigerant leak or
transducer failure
65 Alert Circuit B Loss of Charge Discharge pressure
reading < 10 PSIG for 
30 seconds
Circuit B shut down Manual
66 Alarm Loss of Communication 
with FSM
No communications 
have been received by 
PSIO-1 within 5 minutes 
of last transmission.
FSM forces removed
Runs under own
control
Automatic Wiring faulty or module
failure
67 Alert Circuit A High
Discharge Pressure
SCT > MCT_SP + 5 F
(2.8 C)
Circuit shut down Automatic** Faulty transducer/high 
pressure switch, low/
restricted condenser air/
water flow††
68 Alert Circuit B High
Discharge Pressure
SCT > MCT_SP + 5 F
(2.8 C)
Circuit shut down Automatic** Faulty transducer/high 
pressure switch, low/
restricted condenser air/
water flow††
70 Alert High Leaving Chilled 
Water Temperature
LCW read > LCW Delta
Alarm limit and total
capacity is 100% and 
current LCW > LCW 
reading 1 minute ago 
Alert only. None. Automatic Building load greater 
than unit capacity, low 
water/brine flow, or com-
pressor fault. Check for 
other alarms or alerts.