UNIT OPERATION
Access: Home screen
The Unit Operation screen (see Fig. 47) shows the current unit
operation status.
Fig. 47 — Unit Operation Screen
Click the [PREV] softkey to return to the Home screen, click
the [Alarm] softkey to view the Alarm screen, or click the
[Stpt] softkey to access the unit parameters and to make any
changes to the configuration. See Table 36 for screen function
information.
ARCHIVE-COMMISSIONING
Access: Unit Operation SetPoint screen, [Archive] softkey
The Archive-Commissioning screen (see Fig. 48) allows the user
to save the unit configuration.
Fig. 48 — Archive-Commissioning Screen
Click the [PREV] softkey to return to the Unit Operation
Setpoint screen, or click the [Home] softkey to access the
Home screen. See Table 37 for screen function information.
To archive the configuration:
1. Move the brackets to "No" value on the Initiate Field Archive
line.
2. Press ENTER.
3. Click on the [DECR] or the [INCR] softkeys to change the
value to "Yes".
4. Click [OK] to save the change or [CANCEL] to abandon the
change. If [OK] is clicked, the screen will display "Yes" for a
very short time, then revert to "No," signifying that the con-
figuration has been archived.
HELP
Access: Home screen,[Help] softkey
The Help screen (see Fig. 49) displays a telephone number for
technical support. It also displays the software part number and the
version number.
Fig. 49 — Help Screen
The is nothing that can be adjusted on this screen. Click the
[Home] softkey to return to the Home screen, or click the
[Alarm] softkey to access the Alarm screen.
Table 36 — Unit Operation Screen Functions
FIELD / KEY FUNCTION / INFORMATION
Unit Status
(non-adjustable)
Current unit operating status
Software Mode
(non-adjustable)
Manual_On
: Unit is turned on by the
hand-held BACview or by Virtual BACview
Digital Input
: Unit is turned on by contact
closure (UI-12, terminals 19 and 20)
Keypad Schedule
: Unit is turned on by a
configured schedule
BAS_Command
: Unit is turned on by a
BAS command over the network
Hardware Enabled
(non-adjustable)
FLEX
: 6126 controller only
Flex + EXPANDER
: 6126 controller and
8160 expander module
Reset Sensor Location
(non-adjustable)
Outside Air
Return Air
Mixed Air
Heat/Cool Options
(non-adjustable)
Cooling + HGRH
: Configuration when the
unit has HGRH
Cooling Only
: Configuration when the unit
does not have HGRH
DI Enable Contact:
(non-adjustable)
Off
: Digital input disabled
On
: Digital input enabled
Keypad Schedule Status
(non-adjustable)
On
: Keypad schedule enabled
Off
: Keypad schedule disabled
BAS Command
(non-adjustable)
On
: BAS command is enabled
Off
: BAS command is disabled
Unit Command
(non-adjustable)
Occupied
Unoccupied
Supply Fan Command
(non-adjustable)
On
Off
Return Fan Command:
(non-adjustable)
On
Off
Cooling Percent
(non-adjustable)
0%
to
100%
Coil Configuration
(non-adjustable)
Parallel Evap
Table 37 — Archive-Commissioning Screen
Functions
FIELD / KEY FUNCTION / INFORMATION
Archive Screen
(non-adjustable)
Valid
Initiate Field Archive
(adjustable)
No
LonWorks Network Active
(non-adjustable)
Indicates whether a LonWorks network is
active
LonWorks SI support
Adjustable
Factory Test Status
(adjustable)
Disabled
- default: This is for use by the
factory only. It should never be Enabled.
Enabled
: If Enabled change to Disabled

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Omnizone 50BVC and is the answer not in the manual?

Carrier Omnizone 50BVC Specifications

General IconGeneral
BrandCarrier
ModelOmnizone 50BVC
CategoryAir Conditioner
LanguageEnglish

Related product manuals