50VR-K: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
Pre-Start-up
Use the Start-Up Checklist supplied at the end of this book and proceed
as follows to inspect and prepare the unit for initial start-up:
1. Remove all access panels (see Fig. 22).
2. Read  and  follow  instructions  on  all  DANGER,  WARNING,
CAUTION,  and  INFORMATION  labels  attached  to,  or  shipped
with unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages, such as broken lines, 
loose parts, disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and on unit 
base. Detecting oil generally indicates a refrigerant leak. Leak 
test all refrigerant tubing connections using electronic leak 
detector, or liquid-soap solution. If a refrigerant leak is detected, 
see following Check for Refrigerant Leaks section.
c. Inspect all field- and factory-wiring connections. Be sure that 
connections are completed and tight. Ensure wires do not touch 
refrigerant tubing or sharp sheet metal edges.
d. Inspect coil fins. If damaged during shipping and handling, 
carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that outdoor-fan blade is correctly positioned in fan 
orifice.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain pan and trap are filled with 
water to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts have been 
removed
5. Each  unit  system  has  two  (2)  Schrader-type  ports,  one  low-side
Schrader  fitting  located  on  the  suction  line,  and  one  high-side
Schrader fitting located on the compressor discharge line. Be sure
that caps on the ports are tight.
Start-up
Step 1 – Check Cooling and Heating Control Operation
Start and check the unit for proper control operation as follows:
1. Place room thermostat SYSTEM switch or MODE control in OFF
position.  Observe  that  blower  motor  starts  when  FAN  mode  is
placed  in  FAN  ON  position  and  shuts  down  when  FAN  MODE
switch is placed in AUTO position.
2. Thermostat:
On a typical two stage thermostat, when the room temperature rises
1 or 2 degrees above the cooling control setting of the thermostat,
the thermostat completes the circuit between thermostat terminal R
and  terminals  Y1,  and  G.  These  completed  circuits  through  the
thermostat  connect  the  contactor  coil  (C)  (through  unit  wire Y1)
and  indoor  fan  board  (through  unit  wire  G)  across  the  24-v.
secondary of transformer (TRAN).
On  a typical  two  stage thermostat,  when  the room temperature  is
several degrees above the cooling control setting of the thermostat,
the  thermostat  completes  the  circuit  between  terminal  R  and
terminals Y1, Y2, and G.
3. If your unit contains accessory electric heat, place system switch or
MODE  control  in  HEAT  position.  Set  control  above  room
temperature. Observe that the indoor blower is operating and warm
air  is  flowing  through  the  supply  air  vents  inside  your  home.
Observe that the heating cycle shuts down when the control setting
is satisfied.
If your unit does not contain accessory electric heat and you would
like  to  obtain  it,  please  contact  your  local  dealer  for  more
information.
4. When using an automatic changeover room thermostat place both
SYSTEM  or  MODE  control  and  FAN  mode  stitches  in  AUTO
positions.  Observe  that  unit  operates  in  Cooling  mode  when
temperature  control  is  set  to  “call  for  Cooling”  (below  room
temperature).
NOTE: Once the compressor has started and then has stopped, it should
not be started again until 5 minutes have elapsed.
Step 2 – Check for Refrigerant Leaks
Proceed as follows to locate and repair a refrigerant leak and to charge
the unit:
1. Locate leak and make sure that refrigerant system pressure has been
relieved and reclaimed from both high-and low-pressure ports.
2. Repair leak following Refrigerant Service procedures.
NOTE: Install a  filter drier whenever  the  system has been opened for
repair.
3. Add  a  small  charge  of  R-410A  refrigerant  vapor  to  system  and
leak-test unit.
4. Recover  refrigerant  from  refrigerant  system  and  evacuate  to  500
microns if no additional leaks are found.
5. Charge  unit  with  R-410A  refrigerant,  using  an  electronic  scale.
Refer to unit rating plate for required charge.
Step 3 – Start-Up Adjustments
Complete  the  required  procedures  given  in  the  Pre-Start-Up  section
before  starting  the  unit.  Do  not  jumper  any  safety  devices  when
operating  the  unit.  Do  not  operate  the  unit  in  cooling  mode  when  the
WARNING
!
ENVIRONMENTAL, FIRE, EXPLOSION, ELECTRICAL 
SHOCK HAZARD
Failure to follow this warning could result in personal injury or death
and/or property damage.
1. Follow  recognized  safety  practices  and  wear  protective  goggles
when checking or servicing refrigerant system. 
2. Relieve and recover all refrigerant from system before touching or
disturbing compressor plug if refrigerant leak is suspected around
compressor terminals. 
3. Never  attempt  to  repair  soldered  connection  while  refrigerant
system is under pressure.
4. Do not use torch to remove any component. System contains oil
and refrigerant under pressure.
5. To remove a component, wear protective goggles and proceed as
follows:
a. Shut off electrical power to unit and install lockout tag.
b. Relieve and reclaim all refrigerant from system using both high- 
and low-pressure ports. 
c. Cut component connecting tubing with tubing cutter and 
remove component from unit. 
d. Carefully unsweat remaining tubing stubs when necessary. Oil 
can ignite when exposed to torch flame.
WARNING
!
EXPLOSION HAZARD
Failure  to  follow  this  warning  could  result  in
death,  serious  personal  injury,  and/or  property
damage.
Never use air or gases containing oxygen for leak
testing  or  operating  refrigerant  compressors.
Pressurized  mixtures  of  air  or  gases  containing
oxygen can lead to an explosion.